CHAPTER 1 Installation Data
1.3 Installation Specifications
1.3.3 Installation Specifications (PRIMEQUEST 2800B)
TABLE 1.4 Installation Specifications (PRIMEQUEST 2800B)
| Items |
| Contents | |||
Dimensions | Width |
|
|
| 445(17.52) | |
[mm (in.)] | Depth (*1) |
|
|
| 782(30.79) | |
| Length |
|
|
| 438(17.25) 10U | |
Mass [kg (lb)] (*2) |
|
|
|
| 143(315) | |
Conditions for | Max. calorific | Interruptible power source | 16,992(16,105) | |||
air conditioner | value |
|
|
|
| |
High efficiency power supply (*13) | 16,740(15,866) | |||||
| [kJ/h (BTU/h)] | |||||
|
|
|
|
| ||
| Displacement | Recommended environmental | 12(424) | |||
| [m3/min (ft3/min)] | temperature |
|
| ||
| (*3) | Max. |
| 28(989) | ||
|
|
|
|
|
| |
| Temperature and | At the time |
| Temperature [°C (°F)]] | (*5) | |
| Humidity | of operation |
| Humidity [%RH] | 20 to 80 | |
| conditions (*4) |
|
| Max wet bulb | 29 (84.2) | |
|
|
|
| temperature [°C (°F)]] |
| |
|
| Downtime |
| Temperature [°C (°F)]] | 0 to 50 (32 to 122) | |
|
| (*6) |
| Humidity [%RH] | 8 to 80 | |
|
|
|
| Max wet bulb | 29 (84.2) | |
|
|
|
| temperature [°C (°F)]] |
| |
| Noise [dB] (*7, *8) |
|
|
| 60 | |
| Acoustic power level [B] (*8) |
| 7.8 | |||
| Permissible | At the time of operation (Including | 4.0 (400) (Composite seismic | |||
| Vibration [m/s2 | standby) |
| wave) | ||
| (gal)] | Downtime (*9) |
| 10.0 (1000) (Composite | ||
|
|
|
|
| seismic wave) | |
| Permissible dust level [mg/m3] |
| 0.15 | |||
|
|
|
| |||
Power supply | Input voltage and source resultant pulse number | 200 to 240 VAC±10 % | ||||
conditions |
|
|
|
| 1φ | |
| Frequency and fluctuating Range |
| 50/60 Hz + | |||
|
|
|
|
|
| |
| Max power | At the time |
| Interruptible power | 6.00 kW/6.32 kVA | |
| consumption / | of operation |
| source (*13) |
| |
| apparent power |
|
| High efficiency power | 5.81 kW/6.12 kVA | |
|
|
|
| supply (*13) |
| |
|
| Downtime |
| 0.084 kW | ||
|
|
|
|
|
| |
|
|
|
|
|
| |
| Power factor (*10) |
|
|
| 0.95 or more | |
| Inrush current [A] [Rush hours] (*11) |
| 20 or less | |||
| Leak current [mA] (*12) |
| 6.9 or less |
*1: Dimensions without protrusions
*2: Numeric value when each optional device is mounted for maximum number of options. However, rail for mounting rack (5.7kg) and cable type are not included.
Mass as per the installation configuration can be calculated using formula as shown below. Device mass = 77 + (9.6 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg]
A = Number of mounted SB (Minimum 1 to Maximum 4) B= Number of mounted IOU (Minimum 1 to Maximum 4) C= Number of mounted PSU (Minimum 2 to Maximum 6) D= Number of mounted DU (Minimum 0 to Maximum 2)
*3: There are cases when device is overloaded or when abnormality is detected, FAN rotates at
*4: Protect from condensation.
*5: Temperature condition changes according to the installation location above sea level.
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C (41 to 95°F)
|
|
|
10 |