CHAPTER 2 Connected Information
2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box)
NumberDescription
(1)Free access floor
(2)200 mm (9.8 in)
(3)300 mm (11.8 in) or more
(4)Recipient power distribution
Remarks
The above figure shows an example of
2.6Cutoff Characteristics of Distribution Panel (At the time
of connecting power distribution box)
At the time of connecting the distribution panel through power distribution box, protection should be coordinated so that the breaker of the device (or power distribution box) trips before the breaker of the distribution panel trips. Such protection should be maintained. Therefore, the distribution panel should have the characteristic conditions shown in “TABLE 2.5 Characteristic Condition of Distribution Panel Breaker”. It is necessary to use Distribution panel Breaker suitable to these conditions.
TABLE 2.5 Characteristic Condition of Distribution Panel Breaker
Power input | Device Name |
| Breaker capacity of Distribution panel Breaker |
| ||
| For Japan/general |
| For Europe |
| ||
|
|
| overseas/North America |
|
| |
|
|
|
|
|
| |
AC200 - 240 V | Power distribution box |
| 30A |
| 32A |
|
Cutoff characteristic is
|
|
|
32 |