CHAPTER 2 Connected Information

2.5 Free Access Underfloor Connection of Power Cable

2.4.3 Power Distribution Box and Distribution Panel

Following table shows the power supply cable specifications of power distribution box and distribution panel.

TABLE 2.4 Power Supply Cable Specifications of Power Distribution Box and Distribution Panel

Destination

Plug format

 

Remarks

200V for countries

NEMAL6-30P

Recipient power

NEMA L6-30R (30A-

other than Japan

 

distribution format

220V)

 

 

 

 

200V for Brazil

IEC60309-32A

Recipient power

IEC60309-32A (32A-

 

 

distribution format

250V)

Remarks

Power cable supplied with the device and power cord supplied with the option part, are not used for the power cable which is connected to the device. However, the supplied power cable is not used for the other products.

2.5Free Access Underfloor Connection of Power Cable

If the height of underfloor is less than 300mm (11.8 in.), the power distribution is set to sideways.

FIGURE 2.26 When Underfloor Height is less than 300mm (11.8 in)

NumberDescription

(1)Free access floor

(2)Less than 300mm (11.8 in)

(3)Recipient power distribution

The connector format and cable bend radius of power cable are considered at the time of connecting the power cable of power distribution box (or base cabinet, PCI_Box) under the free access floor. It is recommended that the under floor height is 300 mm (11.8 in) or more.

The recipient power distribution should be arranged near the device.

FIGURE 2.27 When the under floor height is 300 mm (11.8 in) or more.

 

 

 

31

C122-H007-01EN