CHAPTER 1 Installation Data

1.3 Installation Specifications

1.3.4 Installation Specifications (PCI_Box)

TABLE 1.5 Installation Specifications (PCI_Box)

 

 

 

 

Item

 

 

Contents

Dimensions

Width

 

 

 

 

 

482 (18.98)

[mm (in)]

Depth

 

 

 

 

 

740 (29.13)

 

Length

 

 

 

 

 

175 (6.89) 4U

Mass [kg (lb)]

(*2)

 

 

 

 

 

 

35 (77)

Conditions

Max. calorific value [kJ/h (BTU/h)]

 

 

1656 (1570)

for air

Displacement [m3/min

 

FAN low speed (Low)

3 (106)

conditioner

(ft3/min)] (*3)

 

 

 

FAN medium speed (Normal)

4 (141)

 

 

 

 

 

 

FAN high speed (High)

5 (177)

 

Temperature

 

At time of

 

Temperature [°C (°F)]]

(*5)

 

and Humidity

 

operation

 

Humidity [%RH]]

20 to 80

 

condition (*4)

 

 

 

Max wet bulb temperature [°C

29 (84.2)

 

 

 

 

 

 

(°F)]]

 

 

 

 

 

Downtime

 

Temperature [°C (°F)]]

0 to 50 (32 to 122)

 

 

 

 

(*6)

 

Humidity [%RH]]

8 to 80

 

 

 

 

 

 

Max wet bulb temperature [°C

29 (84.2)

 

 

 

 

 

 

(°F)]]

 

 

Noise [dB] (*7, *8)

 

 

 

(Included in

 

 

 

 

 

 

 

 

installation)

 

Acoustic power level [B] (*8)

 

 

(Included in

 

 

 

 

 

 

 

 

installation)

 

Permissibl

 

At the time of operation (Including standby)

4.0 (400) (Composite

 

e Vibration

 

 

 

 

 

 

seismic wave)

 

[m/s2

 

Downtime (*9)

 

 

10.0 (1000)

 

(gal)]

 

 

 

 

 

 

(Composite seismic

 

 

 

 

 

 

 

 

wave)

 

Permissible dust level [mg/m3]

 

 

0.15

Power

Input voltage and source resultant pulse number

200 to 240 VAC±10 %

Supply

 

 

 

 

 

 

 

100 to 120 VAC±10 %

conditions

 

 

 

 

 

 

 

 

Frequency and fluctuating Range

 

 

50/60 Hz + 2/-4%

 

Max

 

At the time of

 

Input voltage: 200 V

450W/475 VA

 

power

 

operation

 

Input voltage: 100 V

460W/485 VA

 

consumpti

 

Downtime

 

Input voltage: 200 V

10W/40VA

 

on /

 

 

 

 

 

Input voltage: 100 V

10W/35 VA

 

apparent

 

 

 

 

 

 

 

 

power

 

 

 

 

 

 

 

 

Power factor (*10)

 

 

More than equal to

 

 

 

 

 

 

 

 

0.95

 

Inrush current [A] [Rush hours] (*11)

Less than or equal to

 

 

 

 

 

 

 

 

25

 

Leak current [mA] (*12)

 

 

Less than or equal to

 

 

 

 

 

 

 

 

3.5

*1: Dimensions without protrusions.

*2: Numeric value when each optional device is mounted for maximum number of options.

*3: If the device is overloaded or if abnormality is detected even though the recommended environmental temperature is used, the FAN rotates at high-speed.

*4: Protect from condensation.

*5: Temperature condition changes according to the installation location above sea level.

For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C (41 to 95°F)

For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to 33°C (41 to 91.4°F)

For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to 31°C (41 to 87.8°F)

For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.2°F)

Error of + 100m in the sea level settings of the location of installation is permissible. *6: Downtime is the condition in which the device is packed and maintained.

 

 

 

12

C122-H007-01EN