CHAPTER 1 Installation Data
1.3 Installation Specifications
1.3.4 Installation Specifications (PCI_Box)
TABLE 1.5 Installation Specifications (PCI_Box)
|
|
|
| Item |
|
| Contents | |
Dimensions | Width |
|
|
|
|
| 482 (18.98) | |
[mm (in)] | Depth |
|
|
|
|
| 740 (29.13) | |
| Length |
|
|
|
|
| 175 (6.89) 4U | |
Mass [kg (lb)] | (*2) |
|
|
|
|
|
| 35 (77) |
Conditions | Max. calorific value [kJ/h (BTU/h)] |
|
| 1656 (1570) | ||||
for air | Displacement [m3/min |
| FAN low speed (Low) | 3 (106) | ||||
conditioner | (ft3/min)] (*3) |
|
|
| FAN medium speed (Normal) | 4 (141) | ||
|
|
|
|
|
| FAN high speed (High) | 5 (177) | |
| Temperature |
| At time of |
| Temperature [°C (°F)]] | (*5) | ||
| and Humidity |
| operation |
| Humidity [%RH]] | 20 to 80 | ||
| condition (*4) |
|
|
| Max wet bulb temperature [°C | 29 (84.2) | ||
|
|
|
|
|
| (°F)]] |
| |
|
|
|
| Downtime |
| Temperature [°C (°F)]] | 0 to 50 (32 to 122) | |
|
|
|
| (*6) |
| Humidity [%RH]] | 8 to 80 | |
|
|
|
|
|
| Max wet bulb temperature [°C | 29 (84.2) | |
|
|
|
|
|
| (°F)]] |
| |
| Noise [dB] (*7, *8) |
|
|
| (Included in | |||
|
|
|
|
|
|
|
| installation) |
| Acoustic power level [B] (*8) |
|
| (Included in | ||||
|
|
|
|
|
|
|
| installation) |
| Permissibl |
| At the time of operation (Including standby) | 4.0 (400) (Composite | ||||
| e Vibration |
|
|
|
|
|
| seismic wave) |
| [m/s2 |
| Downtime (*9) |
|
| 10.0 (1000) | ||
| (gal)] |
|
|
|
|
|
| (Composite seismic |
|
|
|
|
|
|
|
| wave) |
| Permissible dust level [mg/m3] |
|
| 0.15 | ||||
Power | Input voltage and source resultant pulse number | 200 to 240 VAC±10 % | ||||||
Supply |
|
|
|
|
|
|
| 100 to 120 VAC±10 % |
conditions |
|
|
|
|
|
|
| 1φ |
| Frequency and fluctuating Range |
|
| 50/60 Hz + | ||||
| Max |
| At the time of |
| Input voltage: 200 V | 450W/475 VA | ||
| power |
| operation |
| Input voltage: 100 V | 460W/485 VA | ||
| consumpti |
| Downtime |
| Input voltage: 200 V | 10W/40VA | ||
| on / |
|
|
|
|
| Input voltage: 100 V | 10W/35 VA |
| apparent |
|
|
|
|
|
|
|
| power |
|
|
|
|
|
|
|
| Power factor (*10) |
|
| More than equal to | ||||
|
|
|
|
|
|
|
| 0.95 |
| Inrush current [A] [Rush hours] (*11) | Less than or equal to | ||||||
|
|
|
|
|
|
|
| 25 |
| Leak current [mA] (*12) |
|
| Less than or equal to | ||||
|
|
|
|
|
|
|
| 3.5 |
*1: Dimensions without protrusions.
*2: Numeric value when each optional device is mounted for maximum number of options.
*3: If the device is overloaded or if abnormality is detected even though the recommended environmental temperature is used, the FAN rotates at
*4: Protect from condensation.
*5: Temperature condition changes according to the installation location above sea level.
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C (41 to 95°F)
For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to 33°C (41 to 91.4°F)
For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to 31°C (41 to 87.8°F)
For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.2°F)
Error of + 100m in the sea level settings of the location of installation is permissible. *6: Downtime is the condition in which the device is packed and maintained.
|
|
|
12 |