CHAPTER 2 Connected Information 2.3 Power cable connection

100 V Redundant Power Feed Configuration (single power feed, redundant power feed)

It is necessary to arrange two PSUs and two power cables (100 V NEMA 5-15P) for 100 V redundant power feed configuration (single power feed, redundant power feed).

FIGURE 2.22 100 V Redundant power feed configuration (Single power feed, redundant power feed)

Number

Description

(1)Customer distribution panel AC100 V AC#0 system

200 V Standard configuration (single power feed, no redundant power feed) with power distribution box connection

It is necessary to arrange PSU, power cable (200 V IEC 60320 C14) and power distribution box (200 V IEC60320 C134 types) for 200 V Standard configuration (single power feed, no redundant power feed).

FIGURE 2.23 200V Standard configuration (single power feed, no redundant power feed) power distribution

box connection

NumberDescription

(1)Power distribution box (200 V C134 type)

 

 

 