Appendix A Racks

A.1 Rack Mounting

Appendix A Racks

This appendix provides various information on the mounting racks for the PRIMEQUEST 2000 series and PCI_Box.

A.1 Rack Mounting

The PRIMEQUEST 2000 series (including peripheral devices) has been developed and its operation guaranteed with the basic assumption that it is mounted in a Fujitsu rack. For safe use of a unit mounted in a Fujitsu rack, contact the distributor where you purchased your product, or your sales representative.

When mounting the PRIMEQUEST products in a rack manufactured by another company, customers need to confirm on their own responsibility that the rack meets the PRIMEQUEST product specifications and requirements.

See A.2.2 Requirements for mounting in a rack manufactured by another company.

A.2 Rack Mounting Requirements

This section describes rack mounting requirements.

A.2.1 Requirements for mounting in a Fujitsu 19-inch rack

This section explains the requirements for mounting in a Fujitsu 19-inch rack. For safe use of the PRIMEQUEST 2000 series server mounted in a Fujitsu 19-inch rack, observe the mounting requirements described below.

Recommended racks for mounting

The following table lists the recommended racks for mounting the PRIMEQUEST 2000 series server and PCI_Box.

TABLE A.1 Recommended racks for mounting

Fujitsu 19-inch rack

Depth (mm)

Open area ratio

Model 2742

1,050

80%

Model 2737

1,050

80%

Model 2724

1,050

80%

Model 2642

1,050

80%

Model 2624

1,050

80%

Model 2616

1,050

75%

PCR M1 742S

1,050

80%

PCR M1 724S

1,050

80%

PCR M1 642S

1,050

75%

PCR M1 624S

1,050

75%

PCR M1 616S

1,050

75%

PCR M1 742A

1,050

80%

PCR M1 724A

1,050

80%

TABLE A.2 PRIMEQUEST 2000 series external dimensions

Model

Height

Width

Depth

PRIMEQUEST 2000 series

438 mm (10U)

445 mm

782 mm

Note

The Fujitsu 19-inch rack comes with a blank panel covering the front of each empty space that has no mounted device.

If warm exhaust air from the device circulates to the front of the rack and reenters the device, it may cause a temperature alarm and lead to a device failure.

Be sure to use the blank panel to cover the front of an empty space that has no mounted device.

 

 

 

35