Appendix A Racks
A.1 Rack Mounting
Appendix A Racks
This appendix provides various information on the mounting racks for the PRIMEQUEST 2000 series and PCI_Box.
A.1 Rack Mounting
The PRIMEQUEST 2000 series (including peripheral devices) has been developed and its operation guaranteed with the basic assumption that it is mounted in a Fujitsu rack. For safe use of a unit mounted in a Fujitsu rack, contact the distributor where you purchased your product, or your sales representative.
When mounting the PRIMEQUEST products in a rack manufactured by another company, customers need to confirm on their own responsibility that the rack meets the PRIMEQUEST product specifications and requirements.
See A.2.2 Requirements for mounting in a rack manufactured by another company.
A.2 Rack Mounting Requirements
This section describes rack mounting requirements.
A.2.1 Requirements for mounting in a Fujitsu 19-inch rack
This section explains the requirements for mounting in a Fujitsu
Recommended racks for mounting
The following table lists the recommended racks for mounting the PRIMEQUEST 2000 series server and PCI_Box.
TABLE A.1 Recommended racks for mounting
Fujitsu | Depth (mm) | Open area ratio |
Model 2742 | 1,050 | 80% |
Model 2737 | 1,050 | 80% |
Model 2724 | 1,050 | 80% |
Model 2642 | 1,050 | 80% |
Model 2624 | 1,050 | 80% |
Model 2616 | 1,050 | 75% |
PCR M1 742S | 1,050 | 80% |
PCR M1 724S | 1,050 | 80% |
PCR M1 642S | 1,050 | 75% |
PCR M1 624S | 1,050 | 75% |
PCR M1 616S | 1,050 | 75% |
PCR M1 742A | 1,050 | 80% |
PCR M1 724A | 1,050 | 80% |
TABLE A.2 PRIMEQUEST 2000 series external dimensions
Model | Height | Width | Depth |
PRIMEQUEST 2000 series | 438 mm (10U) | 445 mm | 782 mm |
Note
The Fujitsu
If warm exhaust air from the device circulates to the front of the rack and reenters the device, it may cause a temperature alarm and lead to a device failure.
Be sure to use the blank panel to cover the front of an empty space that has no mounted device.
|
|
|