CHAPTER 2 Connected Information 2.3 Power cable connection

200 V Redundant power feed configuration (single power feed, redundant power feed) power distribution box connection

It is necessary to arrange two PSUs, two power cables (200 V IEC60320 C14) and power distribution box (200 V IEC60320 C13×4type) for 200 V redundant power feed configuration (single power feed, redundant power supply).

FIGURE 2.24 200 V Redundant Power Feed Configuration (Single power feed, Redundant Power Feed)

Power Distribution Box Connection

NumberDescription

(1)Power distribution box (200 V C134 type)

200 V Dual Power Feed Configuration with Power Distribution Box Connection

It is necessary to arrange two PSUs, two power cables (200 V IEC60320 C14) and two power distribution boxes (200 V IEC60320 C13×4type) for 200 V dual power feed configuration.

FIGURE 2.25 200 V Dual Power Feed Configuration with Power Distribution Box Connection

NumberDescription

(1)Power distribution box (200V C134 type)

 

 

 