Magnum 6K8-Series Industrial Field Switch Installation and User Guide (04/07)

The following must be adhered to in order to conform to UL requirements:

1.Minimum 18 AWG cable for connection to a Centralized DC power source.

2.Minimum 14 AWG cable for connection to earthing wiring.

3.Use only with Listed 10 A circuit breaker provided in building installation.

4.“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or equivalent.

5.Fastening torque of the lugs on the terminal block: 9-inch pound max.

6.Centralized DC Power Source cable securement, use at least four Minimum 14 AWG cable ties to secure the cable to the rack at least 4 inches apart with the first one located within 6 inches of the terminal block.

C6.0 ORDERING INFORMATION (Optional)

To order the optional Dual-Source -48VDC power supply factory installed, order “Dual-Src48V” as a separate line item following the product model.

Example: Magnum 6K8 -48VDC Dual-Src-48V for the regular DS model

Similarly, order the “Dual –source 24VDC” or “Dual-source 125VDC” as a separate line item following the product model.

Example: Magnum 6K8 -24VDC

C7.0 OPERATION

Operation of the Dual-Source Magnum 6Ks-48VDC, 24VDC and 125VDC Switch models are identical to that of the standard models.