Page 13
Image 13
5500 Series

Auxiliary Control Switches

These switches are located behind the room cabinet under the control panel.

5500 Series

Switches

Description

 

(1)

ALL I2R

Heat pump override - Down - Heat pump operation

 

 

Up - Resistance heat only

(2)

C:FAN

Fan control for cooling operation - Down - Fan Continuous

 

 

Up - Fan Cycle

(3)

H:FAN

Fan control for heating operation - Down - Fan Cycle

 

 

Up - Fan Continuous

(4)

CLASS 2

Remote Thermostat Mode Down - Unit Control

 

 

Up - Remote Thermostat

(5)

LOAD SHED

Load Shedding when connected to Central Desk Control System

 

 

Down - Fan shuts off with unit Up - Fan under “Smart Fan” settings

(6)FREEZ S Freeze Sentinel Override - Down - Freeze Sentinel ON Up - Freeze Sentinel OFF

(7)

CONST FAN

Constant Fan - Fan runs when unit is in STOP mode

(8)

OCCUPIED

Occupancy Sensor Mode - Down - Unit Control

 

 

Up - Occupancy Sensor Connected

Temp L1 - Temp L3

Cooling temperature limiting

(See table at bottom of page)

Temp L4 - Temp L6

Heating temperature limiting

(See table at bottom of page)

 

BOOST

Turns on supplemental heater with heat pump when outdoor temperature is below 45°F

 

DIAGNOS

Used by service technician to briefly operate unit components for diagnostics

Cooling and Heating temperature limits are set independently.

Temperature limiting switches in factory set down position except as noted.

Cooling Temperature Limits

Switches Up

LC Minimum Temperature

Switches Up

LC Minimum Temperature

NONE

1

1,2

2

2,3

1,2,3

1,3

3

60

64

66

68

70

72

74

76

 

 

Heating Temperature Limits

 

 

6

4,6

4,5,6

5,6

5

4,5

4

NONE

65

70

72

74

76

78

80

85

 

 

 

 

 

 

 

 

13

Page 13
Image 13