GE 5500 manual Application Comments, Air Distribution, Recommendation, High Wall Mount - For units

Models: 5500

1 60
Download 60 pages 40.04 Kb
Page 21
Image 21
Application Comments

Application Comments

Use and Care Manual and installation instructions are shipped with Zoneline units. It is important that any air conditioning system be properly sized and applied in order to achieve the desired temperature and humidity levels with the space to be conditioned. Air conditioners are designed primarily to provide heating and cooling with the additional benefit that during operation in the cooling mode, the units also remove some moisture from the conditioned space. The following are some brief application comments on undersizing, oversizing, heating, wall coverings, and air infiltration: all are important in the proper matching of the heating/air conditioning system to the building structure.

Undersizing: If an air conditioner is undersized (cooling capacity is less than required for a specific application), the unit will typically not be able to cool the space down to the desired temperature (thermostat set point), nor be able to remove enough moisture from the air. A result could be a warm and humid or warm and dry conditioned space.

Oversizing: If an air conditioner is oversized (cooling capacity is greater than required for the specific application), the unit will typically cool the space down to the desired temperature (thermostat set point) too quickly. The compressor then begins to cycle on and off. Dehumidification only takes place when the compressor is operating. A typical result in a hot/humid climate could be a cool but excessively humid space.

Heating: Undersizing can result in not being able to maintain the desired temperature level within the conditioned space.

Wall Covering: Use of a non-permeable wall covering (some paints, some wallpapers, and other types of coverings) which severely restricts passage of air or water vapor can cause a severe moisture problem. Typical results could be staining of room surfaces, wall damage, as well as mold and mildew growth in hot/humid climates.

Air Infiltration: Excessive air infiltration can magnify problems associated with undersizing or oversizing of an air conditioner unit and can be the root cause of insufficient cooling, dehumidification, or heating. Some sources of air infiltration include vents, gaps around windows and doors, and improperly sealed floor, ceiling and wall joints.

Recommendation

For the above reasons it is strongly recommended that a professional engineer be retained to match the Zoneline unit with the building structure.

Air Distribution

Zoneline packaged terminal air conditioners and heat pumps discharge air from the top of the unit through reversible 2-position discharge louvers. Unit discharge louvers are reversed by removing the room cabinet from the unit, removing seven screws that hold the louver section in place, removing the louver section and rotating it end for

end, reinstalling the louver section in the room cabinet with the seven screws, and reinstalling the room cabinet on the unit. The unit is shipped from the factory with the discharge louvers at an angle of 50° off vertical. In the alternate position, the louvers will be at an angle of 40° off vertical.

All room cabinets return air through the front of the unit.

High Wall Mount - For units

 

mounted high in the wall, the

 

discharge louvers should be at a

 

setting that provides the most

 

horizontal air discharge.

 

Recommended installation is at

50°

least 3" below the ceiling. In

installations where units are

 

close to the ceiling, the most

 

horizontal discharge angle can

 

be obtained by removing the

 

discharge grill from the room

 

cabinet.

 

Supply Air Throw - One

40°

Zoneline unit should not be required to do a job obviously requiring two or more units.

Units should be located around large rooms according to calculated loads or in such

fashion as to achieve balanced air distribution in all parts of the room. The single unit in the “Incorrect” illustration below obviously cannot condition the entire room.

Add a second unit as shown in the “Correct” illustration.

INCORRECT

OVER 40 FT.

CORRECT

OVER 40 FT.

21

Page 21
Image 21
GE 5500 manual Application Comments, Air Distribution, Recommendation, High Wall Mount - For units, Supply Air Throw - One