For Use With Mechanical 4-Wire Systems Only

Remote Thermostat Control

Multiple Units Connected to One Remote Thermostat (2500 Series)

One remote control thermostat may be used to control multiple resistance heat Zoneline units, however the units may not be wired direct. Since each Zoneline unit has an integral transformer, direct wiring can result in a “bucking”

or “boosting” voltage condition, and is in violation of the National Electric Code. The diagram below shows the correct wiring for such an installation through the use of field supplied isolation relays.

For Use With Mechanical 4-Wire Systems Only

Remote Control (Low Voltage) Wiring

One stage Thermostat Controlling Three Zoneline Units

Resistance Heat Zoneline 2500 Series Units

(Not Applicable on Heat Pump Units)

FIELD SUPPLIED RELAY SPECIFICATIONS

NUMBER OF

RELAY DESIGNATION

UNITS CONTROLLED

R1, R2, and R3

2

POTTER and BRUMFIELD TYPE KA11AY-24 OR EQUIVALENT

3

POTTER and BRUMFIELD TYPE KA14AY-24* OR EQUIVALENT

4

POTTER and BRUMFIELD TYPE KU17A11-24* OR EQUIVALENT

MORE THAN 4

USE COMBINATION OF RELAYS SPECIFIED ABOVE

NOTE: Current draw through thermostat contacts should not exceed 1.0 amps.

*Special order, 100 piece minimum order.