GE 5500 manual The case extension is field fabricated. The

Models: 5500

1 60
Download 60 pages 40.04 Kb
Page 30
Image 30
1. The case extension is field fabricated. The
D
AS REQ'D.

30

METAL CASE EXTENSION FOR WALLS DEEPER THAN 13-1/8" (11-1/8" WITH SUB-BASE)

FIELD FABRICATED – GE RECOMMENDS THE USE OF ONE OF THE DEEPER RAB71 WALL CASES OFFERED AS SPECIAL ORDER ITEMS. SEE PAGE 29.

Zoneline units can be installed in walls of greater depth than the wall case. Where the case recession is less than 3” and where it is possible to waterproof the exposed sides and top of the opening, the suggested procedure is to apply a flashing to the bottom of the wall case as shown on page 29. Where waterproofing is questionable or not possible, or for installations in walls of greater

2. The wall case and extension should be connected prior to installation in the wall opening. A quality grade sealant should be applied to all four (4) butting flanges. Use bolts and nuts or oversized self tapping screws (driven from the wall case to the extension) to attach the two assemblies. Clean all drain holes of excess sealant. The assembly must be free

5.Suggested materials for case extension and flashing should be non-ferrous metals. Minimal acceptable material: Galvanized G-90 painted.

depth, the following is a suggested application procedure. It involves the field fabrication of a case extension. Since the wall case is a water bearing container, the extension likewise must also be water bearing and the connection between the two must be watertight. The case extension must contain splitters to prevent recirculation of the outdoor air circuit.

1. The case extension is field fabricated. The

extension depth “D” should allow for a minimum

outdoor projection of 1/4”. This allows for room

cabinet clearance to the finished wall and ample

surfaces to apply sealant or caulking for a tight

weather seal between the completed wall

case/extension assembly and the wall opening. It

is recommended that the extension be painted

draining.

3. Install flashing, using a quality grade sealant between the flashing and wall as shown in section A-A below.

4. Install the wall case/extension assembly following procedures described for a standard installation. See diagrams below. The assembly should be sealed or caulked to the wall around all four sides both outdoors and indoors.

NOTE: The wall case/extension assembly should be level.

6-1/4" ± 1/4"

SEALANT - ALL

FOUR (4) FLANGES

CAULK*

ROOM

CABINET

WALL -

ANY

CONSTRUCTION

RAB71/77

CASE

 

EXT.

Manual background 1/4" MIN.

Manual background CAULK*

and corner and lap joints be additionally sealed

with a quality grade sealant.

SPLITTER BETWEEN

AIR INTAKE AND

DISCHARGE

CAULK*

CAULK*

SEE DETAIL

SECTION A-A

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

SECTION A-A

BASEPAN/FLANGE DESIGN

SHOWING SEALANT LOCATIONS.

 

 

CUT DRAIN SLOTS

 

1-1/2"

IN BOTH FLANGES

 

(FOUR REQUIRED)

RAB71/77

(4 SIDES)

TO MATCH DRAIN

WALL CASE

EXTENSION

HOLES IN RAB71/77

 

(FIELD

 

 

SUPPLIED)

 

ALL 4 FLANGES

WALL CASE

EXTENSION

2" MIN.

FLASHING (FIELD SUPPLIED)

13-3/4" + D"

ALL 4

SIDES

FLANGES AND

DRAIN HOLE

LOCATIONS

SAME AS ON

WALL CASE

1" WIDE 45° DRIP LIP

FLASHING

ALL 4

SIDES

 

WALL

Page 30
Image 30
GE 5500 manual The case extension is field fabricated. The