GE 5500 Power Connection Kits For Premium Series, 230/208 Volt Installations, Heater, Circuit

Models: 5500

1 60
Download 60 pages 40.04 Kb
Page 42
Image 42
Power Connection Kits For Premium Series (5500)

Power Connection Kits For Premium Series (5500)

The Zoneline 5500 Series units are connected to the building power supply by a unique power connection kit. By utilizing a separate universal power connection (UPC) kit, each unit is capable of providing various outputs of electric resistance heat to more closely meet the heating requirements of the particular room, thereby increasing the installation flexibility of the particular chassis. This power connection kit is the only means of supplying power to the Zoneline chassis and the appropriate kit is determined by the voltage and the desired resistance heat output that may be supported by the branch circuit.

230/208 Volt Installations

Connections to 208 or 230 volt circuits may be made with a line cord power connection kit.

Line Cord Kits consist of a self-aligning 9-pin molded connector that plugs into a mating connector on the Zoneline chassis and insulated line cord with an electrical plug on the end. The configuration of the electrical plug conforms to NEC standards for the circuit amperage and the postion of the wires in the 9-pin connector determines the heater wattage and current requirements when it is plugged into the Zoneline chassis.

Premium

Typical Line Cord

Power Connection Kit

Maximum Cord Extension

Permanent Connection is accomplished by ordering the correct ampacity electrical sub-base to match the Power Cord Kit being used. See page 23 Sub-Base for description.

There may be special requirements by some sites that rigid or flexible conduit be used. (Such as the wall case must be installed flush to finished floor and there is no room for a sub-base.) In these installations the RAK4002B junction box will be needed and the Power Cord/Cord Set will be cut and connected to building wiring inside the RAK4002B junction box. Conduit will be attached to the RAK4002B and to the site supplied building/room junction box where the building wiring enters the room. Wiring will be totally enclosed by conduit and junction boxes.

Line Cord

 

Heater

Circuit

Protective

Kit

Voltage

KW

Ampacity

Device

 

 

 

 

 

RAK3152

230/208

2.55/2.09

15 Amp

15 Amp

 

 

 

 

Time Delay

 

 

 

 

Fuse or Breaker

 

 

 

 

 

RAK3202

230/208

3.45/2.82

20 Amp

20 Amp

 

 

 

 

Time Delay

 

 

 

 

Fuse or Breaker

 

 

 

 

 

RAK3302

230/208

5.00/4.09

30 Amp

30 Amp

 

 

 

 

Time Delay

 

 

 

 

Fuse or Breaker

 

 

 

 

 

 

Receptacle

 

 

 

 

 

 

 

Type

Mfg

Part No

Configuration

 

 

 

 

 

 

 

 

 

 

15 AMP

GE

GE4069

 

 

 

 

 

 

 

Tandem

Hubbell

5661

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEMA6-15R

P&S

5661

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 AMP

GE

GE4182

 

 

 

 

 

 

 

Perpen-

Hubbell

5461

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dicular

P&S

5871

 

 

 

 

 

 

 

NEMA6-20R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 AMP

Hubbell

9330

 

 

 

 

 

 

 

Large

P&S

5930

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tandem

 

 

 

 

 

 

 

 

 

NEMA6-30R

 

 

 

 

 

 

 

 

 

42

Page 42
Image 42
GE 5500 Power Connection Kits For Premium Series, 230/208 Volt Installations, Heater, Circuit, Protective, Ampacity, Type