QUICKSTART GUIDE

If you have successfully logged in you will be presented with a graphic of the particular

Switch to which you are connected.

QS.4.8 Self-test Errors and Meaning

NOTE

Be sure to enable the Ethernet Switch Fail function under Product Setup > User- Programmable Self-tests, and Port Events under Product Setup > Communications > Ethernet Switch.

Activation Setting (set to

Event Name

Event Cause

 

Possible Causes

"Enabled")

 

 

 

 

 

 

 

 

 

 

 

• Loss of Switch power

 

 

 

IP/Gateway/Subnet

 

 

 

 

incompatibility between

 

 

No response has been

 

the CPU and the Switch

 

 

 

module.

ETHERNET SWITCH FAIL

ETHERNET

received from the

UR Port (Port 7) being

Ethernet module after 5

FUNCTION

MODULE OFFLINE

 

configured wrongly/

successive polling

 

 

 

 

blocked

 

 

attempts.

 

 

 

 

Switch IP Address

 

 

 

 

assigned to another

 

 

 

 

device in the same

 

 

 

 

network.

 

 

 

 

 

 

 

An active Ethernet port

Ethernet connection

 

ETHERNET PORT n

 

broken.

PORT n EVENTS

has returned a “Failed”

 

OFFLINE

An inactive port’s events

 

status.

 

 

 

have been enabled.

 

 

 

 

 

 

 

 

 

UR SWITCH MODULE – QUICKSTART GUIDE

QS–31

Page 35
Image 35
GE QS24 UR quick start QS.4.8 Self-test Errors and Meaning, Function Module Offline