1 |
Faults on the I/O Link
A.The Series 90±30 PLC, Series 90±70 PLC, and Power Mate CNC without a separate encoder port handle faults as described below. The following information applies only if there are no other types of devices on the link.
If one of the following faults occurs, communications stop at the fault location. If there are prior devices on the link, they are still able to transfer data with the master. If there are subsequent devices on the link, however, they cannot.
H Power is removed from any device.
H There is a fault in the I/O Link cable such as an open or shorted wire.
H A module fault, software fault, or hardware fault occurs in the master or slave.
MASTER
SLAVE
1
POWER
REMOVED
HERE
SLAVE
2
SLAVE
3
DATA
If the master is a Series 90±70 PLC and one of the following faults occurs, communications continue on the rest of the link.
HA slave has been set up for the wrong amount of data.
HA Series 90±30 slave is in Stop mode.
HThe sequence of slaves on the link is not the same as the sequence expected by the master.
MASTER
SLAVE
1
PLACED IN STOP MODE
SLAVE
2
a45011
SLAVE
3
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DATA |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| B. If the link is connected to any other type of device, including a Power Mate CNC |
| |||||||||||
| that has a separate encoder port, a fault on any device causes the entire link to shut | ||||||||||||
| down as a safety precaution. If that happens, follow this procedure to restore link |
| |||||||||||
| operation. |
| |||||||||||
| 1. | Correct the condition that caused the fault. |
| ||||||||||
| 2. | With the master inactive on the link, clear system errors by power cycling each |
| ||||||||||
|
| CNC slave (turn power off, then on again). |
| ||||||||||
| 3. | Cycle power to each Series 90±30 I/O Link module, to clear the Logicmaster |
| ||||||||||
|
| fault table. |
| ||||||||||
| 4. | Reset the I/O link from the master. |
| ||||||||||