Advance Planning
ADVANCE PLANNING
Ductwork Planning
•These vent hoods are equipped for 10” round ductwork.
•Determine the exact location of the vent hood.
•Plan the route for venting exhaust to the outdoors.
•Use the shortest and straightest duct route possible. For satisfactory performance, duct run should not exceed 150 ft. equivalent length for any duct configurations.
•Refer to “Duct Fittings” chart to compute the maximum permissible length for duct runs to the outdoors.
•Use rigid metal ductwork only.
•Install a roof cap with damper at the exterior opening. Order the cap and any transitions needed in advance.
Ceiling Framing for Adequate Support
•These vent hoods are heavy. Adequate structural support must be provided. The ceiling structure must be capable of supporting the weight of the hood and any inadvertent user contact loads (approximately 300 pounds). The hood support frame will be supported by 2 x 4 cross framing.
Accessory Frames and Duct Covers
•All models are shipped with a support frame and duct covers for ceilings heights of 7’11" to 8’5".
•Optional accessories include telescoping support frames and duct covers to reach 8’6” and up to 10’4” ceiling heights.
•Optional accessories must be ordered with the hood and be on site before final framing and wall finishing.
Mounting the hood without a support frame The distance between the cooking surface and the bottom of the hood must be 30" to 36". In situations where the ceiling is low, the hoods may be secured directly to the ceiling without the supplied frame. Use the bottom of the supplied support frame as a template to locate the mounting holes in the top of the hood. Use shims on the ceiling joists or cross framing in the mounting hole locations. This will allow the mounting screws to engage the recessed keyhole slots in the top of the hood. See Step 2.
POWER SUPPLY
IMPORTANT - (Please read carefully)
WARNING:
FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE PROPERLY GROUNDED.
ATTENTION – POUR DES
RAISONS DE SÉCURITÉ, CET APPAREIL DOIT ÊTRE CORRECTEMENT MIS À LA TERRE.
Remove house fuse or open circuit breaker before beginning installation.
Do not use an extension cord or adapter plug with this appliance. Follow National Electrical Code or prevailing local codes and ordinances.
Electrical Supply
This vent hood must be supplied with 120V, 60Hz, and connected to an individual, properly grounded branch circuit, and protected by a 15 or 20 amp circuit breaker or time delay fuse.
•Wiring must be 2 wire with ground.
•If the electrical supply does not meet the above requirements, call a licensed electrician before proceeding.
•Route house wiring in the ceiling, as close to the installation location as possible. Allow additional length from ceiling joists to reach the junction box on the bottom of the hood support frame.
•Connect the wiring to the house wiring in accordance with local codes.
Grounding Instructions
The grounding conductor must be connected to a ground metal, permanent wiring system, or an
WARNING: The improper connection of
conductor can result in a risk of electric shock. Check with a qualified electrician or service representative if you are in doubt whether the appliance is properly grounded.
AVERTISSEMENT
Le mauvais branchement du fil de mise
àla terre peut causer un choc électrique. En cas de doute, consulter un électricien qualifié ou un technicien pour déterminer si l’appareil est à la terre.