Generac Power Systems 75, 55 Section ENGINE DC CONTROL SYSTEM, Circuit Condition- Fault Shutdown

Models: 65 75 55

1 92
Download 92 pages 22.21 Kb
Page 25
Image 25
CIRCUIT CONDITION- FAULT SHUTDOWN:

Section 5

ENGINE DC CONTROL SYSTEM

CIRCUIT CONDITION- FAULT SHUTDOWN:

The engine mounts a HIGH OIL TEMPERA- TURE SWITCH (HTO) and a LOW OIL PRES-

SURE SWITCH (LOP).

Should engine oil temperature exceed a pre- set value, the switch contacts will close. Wire 85 from the circuit board will connect to frame ground. Circuit board action will then initiate a shutdown.

Should engine oil pressure drop below a safe pre-set value, the switch contacts will close. On contact closure, Wire 85 will be connected to frame ground and circuit board action will initiate an engine shutdown.

The circuit board has a time delay built into it for the Wire 85 fault shutdowns. At STARTUP ONLY the circuit board will wait approximately 6 seconds before looking at the Wire 85 fault shutdowns. Once running after the 6 second time delay, grounding Wire 85 thru either switch will cause an immediate shutdown.