Section 7
DIAGNOSTIC TESTS
7.Inspect the slip rings.
a.If slip rings appear dull or tarnished they may be cleaned and polished with fine sandpaper. DO NOT USE ANY METALLIC GRIT TO CLEAN SLIP RINGS. (A 400 grit wet sandpaper is rec- ommended).
b.After cleaning slip rings, blow away any sandpa- per residue.
RESULTS:
1.Replace bad brushes. Clean slip rings, if necessary.
2.If brushes and rings are good, go to Test 11.
2.If Rotor checks good, perform “Insulation Resistance Test,” on Page 14.
TEST 11- CHECK ROTOR ASSEMBLY
DISCUSSION:
During the “Fixed Excitation Test” (Test 4), if AC out- put voltage did not come up to about
Also see Chapter Three, “INSULATION RESIS-
TANCE TESTS”.
PROCEDURE:
Gain access to the brushes and slip rings. Disconnect Wire 4 and Wire OF from their respective brushes and remove the brush holder. Then, test the Rotor as follows:
1.Set a VOM to its “Rx1” scale and zero the meter.
2.Connect the positive (+) meter test lead to the positive (+) slip ring (nearest the Rotor bearing). Connect the common
ROTOR RESISTANCE *
MODEL: | OHMS |
QP55 4702/4703 | 14.88Ω |
QP65 4704/4705 | 10.81Ω |
QP75 4706/4707 | 14.50Ω − 16.0Ω |
*Resistance values In ohms at 20° C. (68° F.). Actual readings may vary depending on ambient temperature. A tolerance of plus or minus 5% is allowed.
3.Set the VOM to its “Rx1 K” or “Rx10,000” scale and zero the meter.
4.Connect the positive (+) meter test lead to the positive (+) slip ring, the common
RESULTS:
1. Replace the Rotor if it fails the test.
Figure 7-8. – Rotor Assembly
TEST 12 - CHECK MAIN CIRCUIT BREAKER
DISCUSSION:
The main circuit breaker on the generator panel must be closed or no output to the load will be available. A defective breaker may not be able to pass current even though it is in the “ON” position.
Figure 7-9. – Main Breaker (Typical)
PROCEDURE:
Set the coach main breaker to it’s “OFF” position. Check that the appropriate main breaker on the gen- erator panel is set to its “ON” (closed) position. Set a VOM to measure resistance and use it to check for continuity across the breaker terminals.
Page 44