Section 7

DIAGNOSTIC TESTS

INTRODUCTION

The “Diagnostic Tests” in this chapter may be per- formed in conjunction with the “Flow Charts” of Section 6. Test numbers in this chapter correspond to the numbered tests in the “Flow Charts”.

Tests 1 through 17 are procedures Involving prob- lems with the generator's AC output voltage and fre- quency (Problems 1 through 4 in the “Flow Charts”).

Tests 18 through 42 are procedures involving prob- lems with engine operation (Problems 5 through 9 in the “Troubleshooting Flow Charts”).

You may wish to read Section 4, “Measuring Electricity”.

NOTE: Test procedures in this Manual are not necessarily the only acceptable methods for diag- nosing the condition of components and circuits. All possible methods that might be used for sys- tem diagnosis have not been evaluated. If you use any diagnostic method other than the method presented in this Manual, you must ensure that neither your safety nor the product's safety will be endangered by the procedure or method you have selected.

TEST 1- CHECK NO-LOAD VOLTAGE AND

FREQUENCY

DISCUSSION:

The first step in analyzing any problem with the AC generator is to determine the unit's AC output voltage and frequency. Once that has been done, you will know how to proceed with specific diagnostic tests.

PROCEDURE:

1.Set a volt-ohm-milliammeter (VOM) to read AC voltage. Connect the meter test leads across customer connection leads T1 (Red) and T2 (White).

2.Disconnect or turn OFF all electrical loads. Initial checks and adjustments are accomplished at no-load.

3.Start the engine, let it stabilize and warm up.

4.Read the AC voltage.

5.Connect an AC frequency meter across AC output leads T1 (Red) and T2 (White). Repeat the above procedure.

RESULTS:

For units rated 60 Hertz, no-load voltage and frequen- cy should be approximately 122-126 VAC and 61-63 Hertz respectively.

1.If AC voltage and frequency are BOTH correspondingly high or low, go to Test 2.

2.If AC frequency is good but low or residual voltage is indicated, go to Test 3.

3.If AC output voltage and frequency are both “zero”, go to Test 12.

4.If the no-load voltage and frequency are within the stated limits, go to Test 13.

NOTE: The term “low voltage” refers to any volt- age reading that is lower than the unit's rated voltage. The term “residual voltage” refers to the output voltage supplied as a result of Rotor resid- ual magnetism (approximately 5-12 VAC).

TEST 2- CHECK ENGINE GOVERNOR

DISCUSSION:

Rotor operating speed and AC output frequency are proportional. The generator will deliver a frequency of 60 Hertz at 3600 Rotor rpm or 62 Hertz at 3720 Rotor rpm.

The Voltage Regulator should be adjusted to deliver 120 VAC (line-to-neutral) at a frequency of 60 Hertz or 124 VAC (line-to-neutral at 62 Hertz. It is apparent that, if governed speed is high or low, AC frequency and voltage will be correspondingly high or low. Governed speed at no-load is usually set slightly above the rated speed of 60 Hertz (to 62 Hertz), to prevent excessive rpm, frequency and voltage droop under heavy electrical loading.

Figure 7-1. – Governor Adjustment Points

Page 38

Page 40
Image 40
Generac Power Systems 75, 55 Test 1- Check NO-LOAD Voltage Frequency, Test 2- Check Engine Governor, Discussion, Procedure

65, 75, 55 specifications

Generac Power Systems has established itself as a leader in power generation, offering a range of high-performance generators suited for residential and commercial applications. Among its lineup, the Generac 55, 65, and 75 kW generators stand out for their reliability, efficiency, and advanced features.

The Generac 55 kW generator is designed to provide a powerful backup solution for medium to large homes or small businesses. It features a robust engine that delivers dependable performance while maintaining fuel efficiency. One of its key characteristics is the True Power Technology, which produces clean and stable power, ensuring that sensitive electronic devices run smoothly without risk of damage. This generator is equipped with a fully automatic transfer switch, allowing for seamless power transition during outages, with minimal disruption.

Moving to the 65 kW model, it offers increased capacity while retaining the fundamental qualities of the 55 kW version. This unit is particularly suited for larger homes or commercial applications that require greater power demands. The 65 kW generator utilizes Generac’s G-Force engine, known for its durability and reduced maintenance needs. Advanced features such as remote monitoring capabilities allow users to check the generator's status from anywhere, providing peace of mind and convenience.

The 75 kW generator takes performance to the next level, making it ideal for even more significant power needs. It is engineered for both quiet operation and enhanced performance, accommodating a wide range of requirements from residential to larger commercial operations. The 75 kW model includes a full-load voltage regulation system that maintains stable power output under varying loads, safeguarding appliances and equipment.

All three models incorporate advanced air-cooled technology, which enhances their efficiency and operational lifespan. Additionally, their corrosion-resistant enclosures ensure durability even in harsh weather conditions, making them suitable for diverse environments. The intuitive LCD display on each unit provides critical information, including runtime hours and maintenance reminders, empowering users with easy access to the generator's performance data.

Overall, Generac Power Systems' 55, 65, and 75 kW generators represent a commitment to quality, reliability, and innovation in backup power solutions. They are designed to meet the demands of modern power consumption while ensuring peace of mind through robust engineering and advanced technology. Whether for home use or commercial applications, these generators provide an effective means to stay prepared for unexpected power outages.