Section 7
DIAGNOSTIC TESTS
INTRODUCTION
The “Diagnostic Tests” in this chapter may be per- formed in conjunction with the “Flow Charts” of Section 6. Test numbers in this chapter correspond to the numbered tests in the “Flow Charts”.
Tests 1 through 17 are procedures Involving prob- lems with the generator's AC output voltage and fre- quency (Problems 1 through 4 in the “Flow Charts”).
Tests 18 through 42 are procedures involving prob- lems with engine operation (Problems 5 through 9 in the “Troubleshooting Flow Charts”).
You may wish to read Section 4, “Measuring Electricity”.
NOTE: Test procedures in this Manual are not necessarily the only acceptable methods for diag- nosing the condition of components and circuits. All possible methods that might be used for sys- tem diagnosis have not been evaluated. If you use any diagnostic method other than the method presented in this Manual, you must ensure that neither your safety nor the product's safety will be endangered by the procedure or method you have selected.
TEST 1- CHECK NO-LOAD VOLTAGE AND
FREQUENCY
DISCUSSION:
The first step in analyzing any problem with the AC generator is to determine the unit's AC output voltage and frequency. Once that has been done, you will know how to proceed with specific diagnostic tests.
PROCEDURE:
1.Set a
2.Disconnect or turn OFF all electrical loads. Initial checks and adjustments are accomplished at
3.Start the engine, let it stabilize and warm up.
4.Read the AC voltage.
5.Connect an AC frequency meter across AC output leads T1 (Red) and T2 (White). Repeat the above procedure.
RESULTS:
For units rated 60 Hertz,
1.If AC voltage and frequency are BOTH correspondingly high or low, go to Test 2.
2.If AC frequency is good but low or residual voltage is indicated, go to Test 3.
3.If AC output voltage and frequency are both “zero”, go to Test 12.
4.If the
NOTE: The term “low voltage” refers to any volt- age reading that is lower than the unit's rated voltage. The term “residual voltage” refers to the output voltage supplied as a result of Rotor resid- ual magnetism (approximately
TEST 2- CHECK ENGINE GOVERNOR
DISCUSSION:
Rotor operating speed and AC output frequency are proportional. The generator will deliver a frequency of 60 Hertz at 3600 Rotor rpm or 62 Hertz at 3720 Rotor rpm.
The Voltage Regulator should be adjusted to deliver 120 VAC
Figure 7-1. – Governor Adjustment Points
Page 38