Section 7

DIAGNOSTIC TESTS

TEST 38 - CHECK ENGINE / CYLINDER LEAK

DOWN TEST / COMPRESSION TEST

GENERAL:

Most engine problems may be classified as one or a combination of the following:

Will not start.

Starts hard.

Lack of power.

Runs rough.

Vibration.

Overheating.

High oil consumption.

DISCUSSION:

The Cylinder Leak Down Tester checks the sealing (compression) ability of the engine by measuring air leakage from the combustion chamber. Compression loss can present many different symptoms. This test is designed to detect the section of the engine where the fault lies before disassembling the engine.

PROCEDURE:

One or more of the following will usually cause loss of compression:

Blown or leaking cylinder head gasket.

Improperly seated or sticking-valves.

Worn Piston rings or cylinder. (This will also result in high oil consumption).

NOTE: It is extremely difficult to obtain an accu- rate compression reading without special equip- ment. For that reason, compression values are not published for the V-Twin engine. Testing has proven that an accurate compression indication can be obtained using the following method.

PROCEDURE:

1.Remove both spark plugs.

2.Insert a compression gauge into either cylinder.

3.Crank the engine until there is no further increase in pressure.

4.Record the highest reading obtained.

5.Repeat the procedure for the remaining cylinder and record the highest reading.

RESULTS:

1.Remove a spark plug.

2.Gain access to the flywheel. Remove the valve cover.

3.Rotate the engine crankshaft until the piston reaches top dead center (TDC). Both valves should be closed.

4.Lock the flywheel at top dead center.

5.Attach cylinder leak down tester adapter to spark plug hole.

6.Connect an air source of at least 90 psi to the leak down tester.

7.Adjust the regulated pressure on the gauge to 80 psi.

8.Read the right hand gauge on the tester for cylinder pressure. 20 percent leakage is normally acceptable. Use good judgement, and listen for air escaping at the carburetor, the exhaust, and the crankcase breather. This will determine where the fault lies.

9.Repeat Steps 1 through 8 on remaining cylinder.

RESULTS:

Air escapes at the carburetor – check intake valve.

Air escapes through the exhaust – check exhaust valve.

Air escapes through the breather – check piston rings.

Air escapes from the cylinder head – the head gas- ket should be replaced.

CHECK COMPRESSION:

Lost or reduced engine compression can result in (a) failure of the engine to start, or (b) rough operation.

The difference in pressure between the two cylinders should not exceed 25 percent. If the difference is greater than 25 percent, loss of compression in the lowest reading cylinder is indicated.

Example 1: If the pressure reading of cylinder #1 is 165 psi and of cylinder #2, 160 psi, the difference is 5 psi. Divide "5" by the highest reading (165) to obtain the percentage of 3.0 percent.

Example 2: No. 1 cylinder reads 160 psi; No. 2 cylin- der reads 100 psi. The difference is 60 psi. Divide "60" by "160" to obtain "37.5" percent. Loss of compression in No. 2 cylinder is indicated.

If compression is poor, look for one or more of the fol- lowing causes:

Loose cylinder head bolts.

Failed cylinder head gasket.

Burned valves or valve seats.

Insufficient valve clearance.

Warped cylinder head.

Warped valve stem.

Worn or broken piston ring(s).

Worn or damaged cylinder bore.

Broken connecting rod.

Worn valve seats or valves.

Worn valve guides.

NOTE: Refer to Engine Service manual No. 0E2081 for further engine service information.

Page 64

Page 66
Image 66
Generac Power Systems 55, 75, 65 manual Down Test / Compression Test, Adjust the regulated pressure on the gauge to 80 psi

65, 75, 55 specifications

Generac Power Systems has established itself as a leader in power generation, offering a range of high-performance generators suited for residential and commercial applications. Among its lineup, the Generac 55, 65, and 75 kW generators stand out for their reliability, efficiency, and advanced features.

The Generac 55 kW generator is designed to provide a powerful backup solution for medium to large homes or small businesses. It features a robust engine that delivers dependable performance while maintaining fuel efficiency. One of its key characteristics is the True Power Technology, which produces clean and stable power, ensuring that sensitive electronic devices run smoothly without risk of damage. This generator is equipped with a fully automatic transfer switch, allowing for seamless power transition during outages, with minimal disruption.

Moving to the 65 kW model, it offers increased capacity while retaining the fundamental qualities of the 55 kW version. This unit is particularly suited for larger homes or commercial applications that require greater power demands. The 65 kW generator utilizes Generac’s G-Force engine, known for its durability and reduced maintenance needs. Advanced features such as remote monitoring capabilities allow users to check the generator's status from anywhere, providing peace of mind and convenience.

The 75 kW generator takes performance to the next level, making it ideal for even more significant power needs. It is engineered for both quiet operation and enhanced performance, accommodating a wide range of requirements from residential to larger commercial operations. The 75 kW model includes a full-load voltage regulation system that maintains stable power output under varying loads, safeguarding appliances and equipment.

All three models incorporate advanced air-cooled technology, which enhances their efficiency and operational lifespan. Additionally, their corrosion-resistant enclosures ensure durability even in harsh weather conditions, making them suitable for diverse environments. The intuitive LCD display on each unit provides critical information, including runtime hours and maintenance reminders, empowering users with easy access to the generator's performance data.

Overall, Generac Power Systems' 55, 65, and 75 kW generators represent a commitment to quality, reliability, and innovation in backup power solutions. They are designed to meet the demands of modern power consumption while ensuring peace of mind through robust engineering and advanced technology. Whether for home use or commercial applications, these generators provide an effective means to stay prepared for unexpected power outages.