Section 7

DIAGNOSTIC TESTS

TEST 39 - CHECK OIL PRESSURE SWITCH

DISCUSSION:

Also see “Operational Analysis” on Pages 18-23. The Low Oil Pressure Switch is normally-closed, but is held open by engine oil pressure during cranking and startup. Should oil pressure drop below a safe level, the switch contacts will close to ground the Wire 85 circuit. Engine controller board action will then initiate an automatic shutdown.

If the switch fails CLOSED, the engine will crank and start, but will then shut down after a few seconds.

If the switch fails OPEN, low oil pressure will not result in automatic shutdown.

Figure 7-46. – Oil Pressure Switch

PROCEDURE:

1.Check engine oil level. If necessary, replenish oil level to the dipstick “FULL” mark.

2.Set a VOM to its “Rx1” scale and zero the meter.

3.Connect the meter test leads across the switch terminals, with engine shut down. The meter should read “Continuity”. A small amount of resistance is acceptable.

4.Crank the engine. Oil pressure should open the switch contacts at some point while cranking and starting. Meter should then indicate “Infinity”.

5.If the contacts did not open in Step 5, remove the low oil pres- sure switch and connect an oil pressure gauge in it’s place. Start the engine and measure oil pressure. Pressure should be above 10 psi.

RESULTS:

1.In Step 3, if “Continuity” is not indicated, replace the switch.

2.If oil pressure checked good in Step 5, but Step 4 measured “Infinity,” replace the low oil pressure switch.

3.If oil pressure is below 10 psi, determine cause of low oil pres- sure. Refer to Engine Service manual No. 0E2081 for further engine service information. Verify that the oil is the proper vis- cosity for the climate and season.

4.If all steps check GOOD, go to Test 40.

TEST 40 - TEST OIL TEMPERATURE SWITCH

DISCUSSION:

If the engine cranks, starts and then shuts down, one possible cause of the problem may be a high oil tem- perature condition. Protective shutdown is a normal occurrence if the oil temperature switch exceeds approximately 270°F for gasoline units, or 284°F for LP units.

Figure 7-47. – Oil Temperature Switch

PROCEDURE:

1.Remove Wire 85 from Oil Temperature Switch terminal and start the generator. If engine starts and runs now, but shuts down when Wire 85 is connected to the switch terminal, the fol- lowing possibilities exist:

a.Oil temperature is too high.

b.The oil temperature switch has failed closed or is shorted to ground.

2.Remove the switch and place its sensing tip into oil (Figure 7- 48). Place a thermometer into the oil.

3.Connect the test leads of a VOM across the switch terminals. The meter should read “Infinity”.

4.Heat the oil. When oil temperature reaches approximately 270- 284°F., the switch contacts should close and the meter should read “Continuity”.

Page 65

Page 67
Image 67
Generac Power Systems 75, 55, 65 manual Test 39 Check OIL Pressure Switch, Test 40 Test OIL Temperature Switch

65, 75, 55 specifications

Generac Power Systems has established itself as a leader in power generation, offering a range of high-performance generators suited for residential and commercial applications. Among its lineup, the Generac 55, 65, and 75 kW generators stand out for their reliability, efficiency, and advanced features.

The Generac 55 kW generator is designed to provide a powerful backup solution for medium to large homes or small businesses. It features a robust engine that delivers dependable performance while maintaining fuel efficiency. One of its key characteristics is the True Power Technology, which produces clean and stable power, ensuring that sensitive electronic devices run smoothly without risk of damage. This generator is equipped with a fully automatic transfer switch, allowing for seamless power transition during outages, with minimal disruption.

Moving to the 65 kW model, it offers increased capacity while retaining the fundamental qualities of the 55 kW version. This unit is particularly suited for larger homes or commercial applications that require greater power demands. The 65 kW generator utilizes Generac’s G-Force engine, known for its durability and reduced maintenance needs. Advanced features such as remote monitoring capabilities allow users to check the generator's status from anywhere, providing peace of mind and convenience.

The 75 kW generator takes performance to the next level, making it ideal for even more significant power needs. It is engineered for both quiet operation and enhanced performance, accommodating a wide range of requirements from residential to larger commercial operations. The 75 kW model includes a full-load voltage regulation system that maintains stable power output under varying loads, safeguarding appliances and equipment.

All three models incorporate advanced air-cooled technology, which enhances their efficiency and operational lifespan. Additionally, their corrosion-resistant enclosures ensure durability even in harsh weather conditions, making them suitable for diverse environments. The intuitive LCD display on each unit provides critical information, including runtime hours and maintenance reminders, empowering users with easy access to the generator's performance data.

Overall, Generac Power Systems' 55, 65, and 75 kW generators represent a commitment to quality, reliability, and innovation in backup power solutions. They are designed to meet the demands of modern power consumption while ensuring peace of mind through robust engineering and advanced technology. Whether for home use or commercial applications, these generators provide an effective means to stay prepared for unexpected power outages.