ALTERNATE VENT/FLUE DRAIN HOSE CONNECTIONS

Upright installations using the alternate vent/flue outlet will require “right-side only” drain hoses to be connected as follows. Refer to Vent/Flue Pipe and Combustion Air Pipe for details on alternate vent/flue pipe connection.

1.Remove the rubber plug from the right-side drain port on the front cover . Save for use in step 3.

2.Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear right side panel grommet hole.

3.Remove grommet from front right-side panel drain hole. Seal hole in grommet with large end of plug. Reinstall grommet and plug into side panel drain hole.

4.Cut 1/4 inch from the end of the drain port on the externally mounted rubber elbow. Discard cut portion.

5.Insert Tube 1 into rubber elbow drain port and secure with a silver hose clamp. Angle tube toward trap.

6.Cut 17 3/4 inches from the long end of Hose B and discard.

7.Secure straight end of Hose B to exposed end of Tube 1 with a green hose clamp. Route hose toward right side panel grommet holes.

8.Insert short end of one Tube 2 through rear right side panel grommet drain hole. Secure tube to Hose A with a green hose clamp.

9.Insert short end of remaining Tube 2 into Hose B from rubber elbow and secure with green hose clamp. Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or binding.

RUBBER ELBOW

(EXTERNALLY

MOUNTED)

FRONT

 

COVER

HOSE B

DRAIN

PORT

 

RED HOSE

HOSE A

CLAMP

TUBE(S) 2

 

RUBBER

ELBOW

DRAIN PORT

SILVER HOSE CLAMP

TUBE 1

GREEN HOSE

CLAMPS

(3 PLACES)

DRAIN TRAP

Upright “Alternate: Connections - Right Side Only

(Upflow Shown, Counterflow Similar)

22

Page 22
Image 22
Goodman Mfg MH95/ACSH96/AMEH96/ GCH95/GME95/GCH9 Drain Trap, Alternate VENT/FLUE Drain Hose Connections