Goodman Mfg GAS-FIRED WARM AIR FURNACE Manifold Gas Pressure, Rate, Range, Nominal

Models: GAS-FIRED WARM AIR FURNACE MH95/ACSH96/AMEH96/ GCH95/GME95/GCH9

1 56
Download 56 pages 37.33 Kb
Page 35
Image 35
Manifold Gas Pressure

NOTE: If measuring gas pressure at the drip leg or Honeywell VR9205 gas valve, a field-supplied hose barb fitting must be installed prior to making the hose connection. If using the inlet pressure tap on the White-Rodgers 36G54 gas valve, then use the 36G Valve Pressure Check Kit, Goodman Part No. 0151K00000S.

3.Turn ON the gas supply and operate the furnace and all other gas consuming appliances on the same gas supply line.

4.Measure furnace gas supply pressure with burners firing. Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table.

Inlet Gas Supply Pressure

Natural Gas

Minimum:

4.5" w.c.

Maximum:

10.0" w.c.

Propane Gas

Minimum:

11.0" w.c.

Maximum:

13.0" w.c.

If supply pressure differs from table, make the necessary adjust- ments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.

5.Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer. Reinstall plug before turning on gas to furnace.

6.Turn OFF any unnecessary gas appliances stated in step 3.

Gas Line

Gas

Shutoff

Valve

Gas Line

To Furnace

Open To

Atmosphere

Drip Leg Cap

With Fitting

Manometer Hose

Manometer

Measuring Inlet Gas Pressure (Alt. Method)

GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT

Rate CAUTION

TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE. ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR.

Only small variations in gas pressure should be made by adjust- ing the gas valve pressure regulator. The manifold pressure must be measured with the burners operating. To measure and adjust the manifold pressure, use the following procedure.

1.Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.

2.Turn off all electrical power to the system.

3.Outlet pressure tap connections:

a.Honeywell VR9205 valve: Remove the outlet pressure tap plug. Install an 1/8" NPT hose barb fitting into the outlet pressure tap.

b.White-Rodgers 36G54 valve: Back outlet pressure test screw (inlet/outlet pressure tap) out one turn (counterclockwise, not more than one turn).

4.Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or outlet pressure tap (White-Rodgers valve).

5.Turn ON the gas supply.

6.Turn on power and close thermostat “R” and “W1” contacts to provide a call for low stage heat.

7.Measure the gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table shown below.

8.Remove regulator cover screw from the low (LO) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw.

9.Close thermostat “R” and “W2” contacts to provide a call for high stage heat.

10.Remove regulator cover screw from the high (HI) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw.

11.Turn off all electrical power and gas supply to the system.

12.Remove the manometer hose from the hose barb fitting or outlet pressure tap.

13.Replace outlet pressure tap:

a.Honeywell VR9205 valve: Remove the 1/8" NPT hose barb fitting from the outlet pressure tap. Replace the outlet pressure tap plug and seal with a high quality thread sealer.

b.White-Rodgers 36G54 valve: Turn outlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum).

14.Turn on electrical power and gas supply to the system.

15.Close thermostat contacts “R” and “W1/W2” to energize the valve.

Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodg- ers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY!

NOTE: For gas to gas conversion, consult your dealer for appropriate conversion.

Manifold Gas Pressure

Gas

Rate

Range

Nominal

 

 

 

 

Natural

Low Stage

1.7 to 2.3" w.c.

2.0" w.c.

High Stage

3.2 to 3.8" w.c.

3.5" w.c.

 

Propane

Low Stage

5.7 to 6.3" w.c.

6.0" w.c.

High Stage

9.7 to 10.3" w.c.

10.0" w.c.

 

GAS INPUT RATE MEASUREMENT (NATURAL GAS ONLY)

The gas input rate to the furnace must never be greater than that specified on the unit rating plate. To measure natural gas input using the gas meter, use the following procedure.

1.Turn OFF the gas supply to all other gas-burning appliances except the furnace.

2.While the furnace is operating, time and record one complete revolution of the smallest gas meter dial.

35

Page 35
Image 35
Goodman Mfg GAS-FIRED WARM AIR FURNACE, MH95/ACSH96/AMEH96/ GCH95/GME95/GCH9 Manifold Gas Pressure, Rate, Range, Nominal