Goodman Mfg GAS-FIRED WARM AIR FURNACE Troubleshooting Chart, continuously

Models: GAS-FIRED WARM AIR FURNACE MH95/ACSH96/AMEH96/ GCH95/GME95/GCH9

1 56
Download 56 pages 37.33 Kb
Page 43
Image 43
continuously.

TROUBLESHOOTING CHART

 

Symptoms of

Associated

Fault

Possible Causes

Corrective Action

Cautions

 

 

Abnormal Operation

LED Code2

Description(s)

& Notes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Circulator blower runs

 

 

 

 

• Primary limit

• Insufficient conditioned air

• Check primary limit.

• Turn power OFF

 

continuously. No furnace

 

4

 

circuit is open.

over the heat exchanger.

Replace if necessary.

prior to repair.

 

operation.

 

 

 

 

 

Blocked filters, restrictive

• Check filters and

• Replace primary

 

• Integrated control module

 

4 FLASHES

 

ductwork, improper

ductwork for blockage.

switch with proper

 

diagnostic LED is flashing

 

 

circulator blower speed, or

Clean filters or remove

replacement part.

 

 

 

 

 

 

 

FOUR (4) flashes.

 

 

 

 

 

failed circulator blower.

obstruction.

• Replace blower

 

 

 

 

 

 

 

• Faulty primary limit switch.

• Check circulator blower

 

 

 

 

 

 

 

with correct

 

 

 

 

 

 

 

• Loose or improperly

speed and performance.

replacement part.

 

 

 

 

 

 

 

connected wiring.

Correct speed or replace

 

 

 

 

 

 

 

 

 

 

blower if necessary.

 

 

 

 

 

 

 

 

 

 

• Tighten or correct wiring

 

 

 

 

 

 

 

 

 

 

connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Induced draft blower and

 

 

 

 

• Flame sensed

• Short to ground in flame

• Correct short at flame

• Turn power OFF

 

circulator blower runs

 

5

 

 

with no call for

sense circuit.

sensor or in flame

prior to repair.

 

continuously. No furnace

 

 

 

 

heat.

 

sensor wiring.

 

 

 

operation.

 

 

 

 

 

 

 

 

5 FLASHES

 

 

 

 

 

 

• Integrated control module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

diagnostic LED is flashing

 

 

 

 

 

 

 

 

 

 

FIVE (5) flashes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Furnace fails to operate.

 

 

 

 

• Rollout limit open.

• Flame rollout.

• Check burners for proper

• See “Vent/Flue

 

• Integrated control module

 

6

 

• Integrated control

• Misaligned burners,

alignment.

Pipe” section for

 

diagnostic LED is flashing

 

 

 

 

module fuse is

blocked flue and/or air

• Check flue and air inlet

piping details.

 

SIX (6) flashes.

6 FLASHES

blown.

inlet pipe, or failed

piping for blockage,

• Replace induced

 

proper length, elbows,

 

• No furnace operation.

 

induced draft blower.

draft blower with

 

 

 

 

 

 

and termination. Correct

 

 

 

 

 

 

• Loose or improperly

proper replace-

 

 

 

 

 

 

 

as necessary.

 

 

 

 

 

 

 

connected wiring.

• Check rollout limit. Replace

ment part.

 

 

 

 

 

 

 

• Short in 24 volt AC

if necessary.

• Replace inte-

 

 

 

 

 

 

 

control circuits or safety

• Check induced draft

grated control

 

 

 

 

 

 

 

circuits.

blower for proper

module fuse with

 

 

 

 

 

 

 

•Faulty rollout limit.

performance. Replace, if

3A automotive

 

 

 

 

 

 

 

necessary.

fuse.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Tighten or correct wiring

• Read precautions

 

 

 

 

 

 

 

 

connection.

in “Electrostatic

 

 

 

 

 

 

 

 

• Repair short in 24 volt AC

 

 

 

 

 

 

 

 

Discharge”

 

 

 

 

 

 

 

 

control/safety circuit(s).

section of manual.

 

 

 

 

 

 

 

 

• Replace integrated control

• Replace rollout

 

 

 

 

 

 

 

 

module fuse (3A).

limit with correct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

replacement part.

 

 

 

 

 

 

 

 

 

 

 

 

• Normal furnace

 

 

 

 

• Flame sense

• Flame sensor is coated/

• Sand flame sensor.

• Turn power OFF

 

operation.

 

7

 

microamp signal is

oxidized.

• Inspect for proper sensor

prior to repair.

 

• Integrated control module

 

 

 

 

low.

• Flame sensor incorrectly

alignment.

• Clean flame sensor

 

diagnostic LED is

 

7 FLASHES

 

positioned in burner

• Compare current gas

with steel wool.

 

 

 

• See “Vent/Flue

 

flashing SEVEN (7)

 

 

 

 

 

flame.

pressure to rating plate

 

 

 

 

 

 

Pipe” section for

 

flashes.

 

 

 

 

 

• Lazy burner flame due to

info. Adjust as needed.

 

 

 

 

 

 

piping details.

 

 

 

 

 

 

 

improper gas pressure or

 

• See rating plate for

 

 

 

 

 

 

 

combustion air.

 

 

 

 

 

 

 

 

 

proper gas

 

 

 

 

 

 

 

 

 

pressure.

 

 

 

 

 

 

 

 

 

 

 

 

• Furnace not operating.

 

 

 

 

• Problem with

• Improperly connected

• Check and correct wiring

• Turn power OFF

 

 

 

 

 

 

• Integrated control module

 

 

 

 

igniter circuit.

igniter.

from integrated control

prior to repair.

 

 

 

 

 

• Bad igniter.

 

diagnostic LED is

 

 

 

 

 

module to igniter.

• Replace igniter

 

 

 

 

 

 

• Poor unit ground.

 

flashing EIGHT (8)

 

 

 

 

 

•Replace bad igniter.

with proper

 

 

8 FLASHES

 

• Poor burner ground.

 

flashes.

 

 

•Check and correct unit

replacement part.

 

 

 

 

 

 

• Faulty integrated control

 

 

 

 

 

 

 

module.

ground wiring.

• Read precautions

 

 

 

 

 

 

 

 

• Replace bad integrated

in “Electrostatic

 

 

 

 

 

 

 

 

Discharge”

 

 

 

 

 

 

 

 

control module.

 

 

 

 

 

 

 

 

section of manual.

 

 

 

 

 

 

 

 

 

 

 

 

• Induced draft blower runs

 

 

 

 

• Polarity of 115

• Polarity of 115 volt AC

• Review wiring diagram to

• Turn power OFF

 

continuously. No furnace

 

C

 

or 24 volt

power to furnace or

correct polarity.

prior to repair.

 

operation.

 

 

 

 

power is

integrated control module

• Verify proper ground.

 

 

 

 

 

 

 

is reversed.

 

 

 

 

 

 

reversed.

 

 

 

• Integrated control module

CONTINUOUS

• Red and blue wires to

Correct if necessary.

 

 

 

diagnostic LED is flashing

 

transformer are reversed.

• Reverse red and blue

 

 

 

continuously.

 

FLASHING

 

• Poor unit ground.

wires connected to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transformer.

 

 

 

• LED is steady on

 

STEADY

• Normal operation.

 

 

 

 

 

 

 

ON

 

 

 

 

 