DIRECT VENT TERMINAL CLEARANCES

 

 

Canadian Installations1

U.S. Installations 2

A=

Clearance above grade,

12 in. (30 cm)

12 in. (30 cm)

 

veranda, porch, deck or

 

 

 

balcony. (See 1.24.6-i(9)b.)

 

 

 

 

 

 

B=

Clearance to window or

6 in. (15 cm) for appliances

6 in. (15 cm) for appliances

 

door that may be opened.

10,000 Btuh (3 kW), 12 in. (30 cm) for

10,000 Btuh (3 kW), 9 in. (23 cm) for

 

 

appliances > 10,000 Btuh (3 kW) and

appliances > 10,000 Btuh (3 kW) and

 

 

100,000 Btuh (30 kW), 36 in. (91 cm)

50,000 Btuh (15 kW), 12 in. (30 cm) for

 

 

for appliances > 100,000 Btuh (30

appliances > 500,000 Btuh (15 kW).

 

 

kW).

 

 

 

 

 

C=

Clearance to permanently

*

*

 

closed window.

 

 

 

 

 

 

D=

Vertical clearance to ventilated soffit

*

*

 

located above the terminal within a

 

 

 

horizontal distance of 2 feet (61 cm)

 

 

 

from the center line of the terminal.

 

 

 

 

 

 

E=

Clearance to unventilated soffit.

*

*

 

 

 

 

F=

Clearance to outside corner.

*

*

 

 

 

 

G=

Clearance to inside corner.

*

*

 

 

 

 

H=

Clearance to each side of center

3 ft. (91 cm) within a height 15 ft.

*

 

line extended above meter/regulator

(4.5 m) above the meter/regulator

 

 

assembly.

assembly.

 

 

 

 

 

 

 

Canadian Installations 1

U.S. Installations 2

I=

Clearance to service

3 ft. (91 cm).

*

 

regulator vent outlet.

 

 

 

 

 

 

J=

Clearance to nonmechanical air

6 in. (15 cm) for appliances 10,000

6 in. (15 cm) for appliances 10,000

 

supply inlet to building or the

Btuh (3 kW), 12 in. (30 cm) for

Btuh (3 kW), 9 in. (23 cm) for

 

combustion air inlet to any other

appliances > 10,000 Btuh (3kW) and

appliances > 10,000 Btuh (3kW) and

 

appliance.

100,000 Btuh (30 kW), 36 in. (91 cm)

50,000 Btuh (15 kW), 12 in. (30 cm) for

 

 

for appliances > 100,000 Btuh (30 kW).

appliances > 50,000 Btuh (15 kW).

 

 

 

 

K=

Clearance to a mechanical

6 ft. (1.83 m)

3 ft. (91 cm) above if within

 

air supply inlet.

 

10 ft. (3 m) horizontally.

 

 

 

 

L=

Clearance above paved sidewalk or

7 ft. (2.13m) †

*

 

paved driveway located on public

 

 

 

property.

 

 

 

 

 

 

M=

Clearance under veranda, porch,

12 in. (30 cm) ‡

*

 

deck or balcony.

 

 

1In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.

2In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single fanily dwellings and serves both dwellings.

Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:

“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation instruction.”

OTHER THAN DIRECT VENT TERMINAL CLEARANCES

 

 

Canadian Installations 1

U.S. Installations 2

A=

Clearance above grade,

12 in. (30 cm)

12 in. (30 cm)

 

veranda, porch, deck or

 

 

 

balcony. (See 1.24.6-i(9)b.)

 

 

 

 

 

 

B=

Clearance to window or

6 in. (15 cm) for appliances

4 ft. (1.2 m) below or to side of

 

door that may be opened.

10,000 Btuh (3 kW), 12 in. (30 cm) for

opening; 1 ft. (300 m) above opening.

 

 

appliances > 10,000 Btuh (3 kW) and

 

 

 

100,000 Btuh (30 kW), 36 in. (91 cm)

 

 

 

for appliances > 100,000 Btuh (30

 

 

 

kW).

 

 

 

 

 

C=

Clearance to permanently

*

*

 

closed window.

 

 

 

 

 

 

D=

Vertical clearance to ventilated soffit

*

*

 

located above the terminal within a

 

 

 

horizontal distance of 2 feet (61 cm)

 

 

 

from the center line of the terminal.

 

 

 

 

 

 

E=

Clearance to unventilated soffit.

*

*

 

 

 

 

F=

Clearance to outside corner.

*

*

 

 

 

 

G=

Clearance to inside corner.

*

*

 

 

 

 

H=

Clearance to each side of center

3 ft. (91 cm) within a height 15 ft.

*

 

line extended above meter/regulator

(4.5 m) above the meter/regulator

 

 

assembly.

assembly.

 

 

 

 

 

 

 

Canadian Installations1

U.S. Installations2

I=

Clearance to sevice

3 ft. (91 cm).

*

 

regulator vent outlet.

 

 

 

 

 

 

J=

Clearance to nonmechanical air

6 in. (15 cm) for appliances 10,000

4 ft. (1.2 m) below or to side of

 

supply inlet to building or the

Btuh (3 kW), 12 in. (30 cm) for

opening; 1 ft. (300 m) above opening.

 

combustion air inlet to any other

appliances > 10,000 Btuh (3kW) and

 

 

appliance.

100,000 Btuh (30 kW), 36 in. (91 cm)

 

 

 

for appliances > 100,000 Btuh (30 kW).

 

 

 

 

 

K=

Clearance to a mechanical

6 ft. (1.83 m)

3 ft. (91 cm) above if within

 

air supply inlet.

 

10 ft. (3 m) horizontally.

 

 

 

 

L=

Clearance above paved sidewalk or

7 ft. (2.13m) †

7 ft. (2.13m)

 

paved driveway located on public

 

 

 

property.

 

 

 

 

 

 

M=

Clearance under veranda, porch,

12 in. (30 cm) ‡

*

 

deck or balcony.

 

 

1In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.

2In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.

A vent shall not terminate directly above a sidewalk or paveable driveway that is located between two single family dwellings and serves both dwelling.

Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:

“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation instruction.”