Goodman Mfg GAS-FIRED WARM AIR FURNACE Hose B, Front, Hose A, Clamp, Tubes, Drain Port, Cover

Models: GAS-FIRED WARM AIR FURNACE MH95/ACSH96/AMEH96/ GCH95/GME95/GCH9

1 56
Download 56 pages 37.33 Kb
Page 25
Image 25
GREEN HOSE

LEFT SIDE DOWN

Horizontal installations with the left side panel down will require drain hoses to be connected to the left side front cover drain port and the side drain port on the rubber elbow.

1.Remove the rubber plug from the front cover left (down) side drain port.

2.Relocate the front cover pressure switch hose connection from the right side (as shipped) pressure tap to the left (down) side tap. The pressure switch hose must be connected to the down side to guard against blocked drain conditions. Cut hose to appropriate length to minimize sagging. Plug right (unused) pressure tap with plug removed from left side.

3.Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear left (down) side panel grommet holes. NOTE: For left side drainage, grommets must be relocated to left side panel.

4.Remove the rubber cap from the side drain port on the rubber elbow.

5.Secure the short end of Hose B to rubber elbow side drain port using a green hose clamp. NOTE: For left side drainage, route hose to far left (down) side panel grommet holes. NOTE: Horizontal left side connections (when using new side port drain elbow) does not require connecting a hose to the induced draft blower housing.

6.Cut 5 1/2 inches straight length from the long end of each Tube 2 and discard radius ends.

7.Insert approximately one inch of each Tube 2 through left side panel grommet hole. Secure tubes to Hose A and Hose B with a green hose clamps. NOTE: Tube must reach bottom of trap. Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.

For details concerning mounting of the drain trap, refer to Conden- sate Drain Lines and Drain Trap - Horizontal Drain Trap Mounting.

 

 

GREEN HOSE

 

 

CLAMP

 

 

HOSE B

 

FRONT

HOSE A

 

COVER

 

PRESSURE

 

 

TAP

 

 

 

GREEN HOSE

 

 

CLAMP

LEFT SIDE

FRONT COVER

TUBE(S) 2

PANEL

 

 

DRAIN PORT

 

 

RED HOSE CLAMP

DRAIN TRAP

SIDE PANEL

GROMMET

HOLES

Horizontal Connections - Left Side Down

(Upflow Shown, Counterflow Similar)

HORIZONTAL DRAIN TRAP MOUNTING (LEFT OR RIGHT SIDE PANEL)

1.Position the drain trap against side panel with drain tubes inserted into trap. Note that the trap may be orientated with the outlet facing either the furnace’s top cover or base pan.

2.Secure drain trap to side panel at the dimples or crosshairs located on either side of the grommet drain holes.

3.Confirm that tubes reach bottom of drain trap and that all hoses maintain a downward slope and are not kinked or binding.

4.Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.