Manual background Chimney or Gas Vent

NOTE: Each opening must have a free area of not less than one square inch per 1000 BTU of the total input rating of all equip- ment in the enclosure, but not less than 100 square inches.

Manual backgroundManual background Opening

Water

Furnace Heater

Manual backgroundManual background Opening

Manual background Chimney or Gas Vent

Ventilation louvers (each end of attic)

NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the

total input rating of all equipment in the enclosure.

 

 

 

 

 

Outlet Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

Heater

 

 

Furnace

Inlet air duct

 

 

 

 

 

 

 

 

 

 

 

 

 

[ends 1 ft (300 mm)

 

 

 

 

 

above floor]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Located in Confined Spaces; All Air from Inside Building.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Located in Confined Spaces; All Air from Outdoors

See 5.3.3-a.

(b) All Air from Outdoors: The confined space shall be provided with

 

 

 

 

 

 

 

 

Through Ventilated Attic. See 5.3.3-b.

 

 

 

3. When communicating with the outdoors through horizontal ducts,

two permanent openings, one commencing within 12 inches of the

 

 

 

top and one commencing within 12 inches of the bottom of the

 

 

 

 

 

each opening shall have a minimum free area of 1 square inch per

enclosure. The openings shall communicate directly, or by ducts,

 

 

 

 

 

2,000 BTU per hour of total input rating of all equipment in the

with the outdoors or spaces (crawl or attic) that freely communicate

 

 

 

 

 

enclosure.

with the outdoors.

 

 

 

 

 

 

 

Chimney or Gas Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 BTU

per hour of total input rating of all equipment in the enclosure.

 

 

 

 

 

 

 

NOTE: The air duct openings

 

 

 

 

 

 

 

 

 

 

 

must have a free area of not

 

Chimney or Gas Vent

 

 

 

 

 

 

 

less than one square inch per

 

 

 

Ventilation louvers

 

 

 

 

 

 

 

2000 BTU of the total input

 

 

 

 

 

 

 

 

 

 

rating of all equipment in the

 

 

 

(each end of attic)

 

 

 

 

 

 

Outlet air duct

enclosure*.

 

 

 

NOTE: The inlet and outlet air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

openings must each have a free

 

 

 

 

 

 

 

 

 

 

 

area of not less than one square

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inch per 4000 BTU of the

 

 

 

Heater

 

 

 

 

 

 

Furnace

 

 

 

 

 

 

 

 

 

 

 

 

 

total input rating of all equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in the enclosure.

 

 

 

 

 

 

Inlet air duct

 

 

 

 

 

 

 

 

 

 

 

 

 

Outlet Air

Water

 

 

 

 

 

Heater

 

 

 

*If the appliance room is located against an outside wall and the air openings communicate directly with the

 

 

 

Furnace

Inlet Air

 

 

 

 

 

 

 

outdoors, each opening shall have a free area of not less than one square inch per 4,000 BTU per hour of

 

 

 

 

 

 

 

 

Alternate

 

 

 

 

 

the total input rating of all appliances in the enclosure.

 

 

 

 

 

Equipment Located in Confined Spaces; All Air from Outdoors.

air inlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See 5.3.3-b.

 

 

 

 

 

 

 

 

 

Ventilation louvers for unheated crawl space

Equipment Located in Confined Spaces; All Air from Outdoors— Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated Attic. See 5.3.3-b

2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure.

4.When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall not be less than 3 inches.

NOTE: The single opening must have

a free area of not less than oneManual background Chimney or Gas Vent square inch per 3000 BTU of

the total input rating of all equip-

ment in the enclosure, but not less than the sum of the areas of all vent connectors in the confined space.

 

 

 

 

 

 

 

Opening

 

 

 

 

 

 

 

Alternate

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

Opening

 

 

 

 

Heater

 

 

 

 

 

 

 

 

 

 

 

Location

Furnace

 

 

 

 

 

 

 

 

 

 

Equipment Located in Confined Spaces; All Air from Outdoors -

Single Air Opening. See 5.3.3-b.

11

Page 11
Image 11