10.3Air Purging

Installation Service

10.INSTALL OUTDOOR UNIT

10.3Air Purging

Air and moisture remaining in the refrigerant system have undersirable effects as indicated below. Therefore, they must be purged completely.

Pressure in the system rises

Operating current rises

Cooling (or heating) efficiency drops

Moisture in the air may freeze and block capillary tubing.

Water may lead to corrosion of parts in the refrigerant system.

AIR PURGING WITH A VACUUM PUMP (FOR TEST RUN)

1.Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Noted that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.

2.Using a adjustable wrench or box wrench, remove the valve caps from the service on both narrow and wide tubes.

3.Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig.35)

CAUTION

Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this pupose. The "Hi" knob of the manifold valve must always be kept closed.

4.With the "Lo" knob of the manifold valve open, run the vacuum pump. The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:

Table 3

Required time for evacuation when capacity of 100 liter/h vacuum pump is used

If tubing length is

If tubing length is

less than 7 m

more than 7 m

10 min. or more

15 min.or more

 

 

Indoor unit

Outdoor unit

Manifold valve

Pressure

 

gauge
Lo Hi

 

Vacuum pump

Fig.35

NOTE The require time in the table 3 is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.

31

Page 33
Image 33
Haier KC18AGH 10.3Air Purging, Install Outdoor Unit, Installation Service, Air Purging With A Vacuum Pump For Test Run