Installation Service
10.INSTALL OUTDOOR UNIT
10.4Tubing Length
Install unit within the maximum elevation different (H) above or below the outdoor unit and within a tatal tubing length (L) from the outdoor unit as detailed showed in Table 4 and Fig.37.
INDOOR
UNIT
Elevation difference (H)
Tubing length (L)
OUTDOOR
UNIT
|
|
|
|
| Fig. 37 | |
Table 4 |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| Max. Allowable Tubing | Limit of Tubing | Limit of Elevation |
| Required Amount of |
| Model | Length at Shipment | Length (L) | Different (H) |
| Additional Refrigerant |
|
| (m)*1 | (m) | (m) |
| (g/m)*2 |
| C18AM | 7.5 | 25 | 7 |
| 30 |
|
|
|
|
|
|
|
| C18AGH | 5.0 | 25 | 7 |
| 30 |
|
|
|
|
|
|
|
*1 Standard tubing length is 5m for C18AGH & 7.5m for C18AM.
*2 If total tubing length becomes 5m / 7.5m to 25m, charge additional refrigerant (R22) acording to table above. No additional charge of compressor oil is necessary.
10.5Outdoor Condensation Drainage (Heat Pump model only)
When the unit is heating and cooling type, the condensing water and defrosting water can be drained out reliably through the drainage pipe.
How to install:
Install the outdoor drain nozzle in Ø 25 hole on the base plate, and joint the drain pipe to the drain nozzle, so that the waste water formed in the outdoor unit can be drained out to a proper place.(Fig.38)
Chasis
Drain Nozzle
Fig. 38
10.6 Accessories
Table 5 listed the accessories supplied with the unit.
Table 5
Parts
Silver Ion filter
Remote control unit
Signal control wire
Power connection wire
Figure
FAN OPER | C | ONOFF | ON/OFF MODE | - + | FAN | CLOCK | BLOW TEMP | TURBO SLEEP LIGHT |
#
Q’ty | Parts | Figure | Q’ty | Parts | Figure | Q’ty |
2 | AAA alkaline |
| 2 | Tapping | 4.2 x 25 mm | 10 |
battery |
| screw | ||||
|
|
|
|
| ||
| Remote control |
|
|
|
|
|
1 | holder |
| 1 | Ins. tube |
| 1 |
| (Optional Part) |
|
|
|
|
|
1 | Drain nozzle* | # | 1 | Putty |
| 1 |
|
| |||||
1 | Drain cap* | # | 3 | Flare Nut | 0 | 1 |
|
*Packed in the outdoor unit
#Heat pump model only
33