G

v

D A

 

E

 

 

 

 

v

 

 

 

L

B

 

 

 

 

 

B

 

 

v

v

B

 

v

 

 

 

F

v

 

v

 

 

 

 

A

R

H

U.S.

 

(3 FT)

 

I M

X

v

 

J or K

M

N

P

Q

(See Note 2)

V

T

VS Electrical Service

D*

V

S V

V

= VENT TERMINAL

X = AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

A

=

12"

clearances above grade, veran-

 

 

 

6 ft. (Canada)

......... clearance to a mechanical air

 

 

(See Note 1)

da, porch, deck or balcony

 

 

 

 

 

supply inlet

 

 

B

=

12"

clearances to window or door

L**

=

7 ft. ......................... clearance above paved side-

 

 

 

that may be opened, or to per-

 

 

 

 

 

walk or a paved driveway locat-

 

 

 

manently closed window.

 

 

 

(See Note 1)

ed on public property

D*

=

18"

vertical clearance to unventilat-

M*** =

18"

 

clearance under veranda,

 

 

 

 

 

porch, deck, balcony or over-

 

 

 

ed soffit or to ventilated soffit lo-

 

 

 

 

 

 

 

 

 

 

 

 

 

hang

 

 

 

 

 

cated above the terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

42”

vinyl

 

 

 

 

*48” min

for vinyl clad soffits and below

 

 

 

 

 

 

 

N

=

6” ........................... non-vinyl sidewalls

 

 

 

electrical service

 

 

 

 

 

 

12” ......................... vinyl sidewalls

F

=

9"

clearance to outside corner

 

 

 

P

=

8 ft.

 

 

 

 

G

=

6"

clearance to inside corner

 

 

 

 

 

 

 

 

 

 

 

 

 

H

=

3 ft. (Canada)

not to be installed above a gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QMIN

 

RMAX

 

 

 

 

meter/regulator assembly within

 

 

 

 

 

 

 

 

 

 

3 feet (90cm) horizontally from the

 

 

1 cap

 

3 feet

 

2 x Q ACTUAL

 

 

 

 

center-line of the regulator

 

 

2 caps

 

6 feet

 

1 x Q ACTUAL

 

I

=

3 ft

clearance to gas service regu-

 

 

3 caps

 

9 feet

 

2/3 x Q ACTUAL

 

J

=

9" (U.S.A.)

lator vent outlet

 

 

4 caps

 

12 feet

 

1/2 x Q ACTUAL

 

 

 

 

 

 

 

 

 

 

QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL

 

 

 

12" (Canada)

clearance to non-mechanical air

 

 

 

 

 

 

supply inlet to building or the

S

=

6" MIN................... clearance from sides of elec-

 

 

 

combustion air inlet to any other

 

 

 

(See Note 5)

trical service

 

 

 

appliance

 

 

 

K

=

3 ft. (U.S.A.)

T

=

12" MIN. ................ clearance above electrical

 

 

 

 

 

 

 

 

(See Note 5)

service

 

 

**a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

***only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor or meets Note 2.

NOTE 1: On private property where termination is less than 7 feet

above a sidewalk, driveway, deck, porch, veranda or balcony, use of

a listed cap shield is suggested.

NOTE 2: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for

vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum

between termination caps. 2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap. 3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap.

Figure 18. Vent Termination Minimum Clearances

NOTE 3: Local codes or regulations may require different clearances.

NOTE 4: Termination caps may be hot. Consider their proximity to doors or other traffic areas.

NOTE 5: Location of the vent termination must not interfere with access to the electrical service.

WARNING: In the U.S: Vent system termination is NOT permitted

in screened porches. You must follow side wall, overhang and

ground clearances as stated in the instructions.

In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow all side walls, overhang and ground clearances as stated in the instructions.

Heat & Glo assumes no responsibility for the improper perfor- mance of the fireplace when the venting system does not meet these requirements.

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.

24

Heat & Glo • CFX-CRESCENT705-900 Rev. P • 12/07

Page 24
Image 24
Hearth and Home Technologies CFX-Crescent owner manual Vent Termination Minimum Clearances