Hearth and Home Technologies CFX-Crescent Step Positioning Leveling, Securing Fireplace

Models: CFX-Crescent

1 38
Download 38 pages 31.85 Kb
Page 27
Image 27

Step 4

Positioning,

Leveling, and

Securing the

Fireplace

NOTE: Before positioning fireplace into framing re- move Finishing Strips that are secured to right side of fireplace. The strips will be used in the finishing process. Refer to Finish- ing Variations addendum included in manual bag.

To properly position, level, and secure the fireplace:

1.Place the fireplace into position.

2.Level the fireplace from side to side and from front to back.

3.Fold out top four framing tabs to be flush with (2) bottom tabs as shown (Figure 21).

4.Secure the fireplace to the framing by nailing or screwing to all six fram- ing tabs.

FINISHING

STRIPS

Figure 20. Remove Finishing Strips

WARNING: To secure proper clearances the front framing header must be installed on its narrow edge and to the front of the frame.

TOP (4)

FRAMING

TABS

BOTTOM (2)

FRAMING TABS

Figure 21. Proper Positioning, Leveling, and

Securing of a Fireplace

Step 5

The Gas Control

System

The gas control system used with this model is Intermittent Pilot Ignition (IPI). This system in- cludes a 3V control valve. electronic module, and intermittent pilot.

!WARNING: THIS UNIT IS NOT FOR USE WITH SOLID FUEL.

Intermittent Pilot Ignition (IPI) System

IGNITOR

Figure 22. Gas Control System

!WARNING: CONTINUOUS 110-120 VAC SER-

VICE MUST BE WIRED DIRECTLY TO THE FIREPLACE JUNCTION BOX .

Heat & Glo • CFX-CRESCENT705-900 Rev. P • 12/07

27