Heat & Glo • 6000TRSI-AUC • 2078-900 Rev. G • 12/06
NOTES: 1. All distances are measured vertically or horizontally along the wall to a point
in line with the nearest part of the terminal.
2. Prohibited area below electricity meter or fuse box extends to ground level.
3. See clause 5.13.6.6 for restrictions on a flue terminal under a roofed area.
4. See Appendix J, Figure J1(a) and J2(a) for clearances required from a flue
terminal to a LP Gas cylinder. A flue terminal is considered to be a source of ignition.
MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS
OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES
FIGURE 1.4
CLEARANCES 'n' (mm)Space heaters All other appliances
Up to 50 MJ/h
input UP to 50 MJ/h
input Over 50 MJ/h &
up
to 150 MJ/h
Over 150 MJ/h
input
150 500 1000 1500
a - Below eaves, balconies or other projections: MIN. CLEARANCE (mm)
Appliances up to 50 MJ/h input ...........................................................................................300
Appliances over 50 MJ/h input ............................................................................................500
b - From the ground or above a balcony ......................................................................................300
c - From a return wall or external corner ..................................................................................... 500
d - From a gas meter (M) ...........................................................................................................1000
e - From an electricity meter or fuse box (P) ............................................................................... 500
f - From a drain or soil pipe .........................................................................................................150
g - Horizontally from any building structure (unless appliance approved
for closer installation) or obstruction facing a terminal......................................................... 5 00
h - From any other flue terminal, cowl, or combustion air intake ...............................................50 0
j - Horizontally from an openable window, door, non-mechanical air
inlet, or any other opening into a building, with the exception of
sub-floor ventilation:
Appliances up to 150 MJ/h input ......................................................................................... 5 00
Appliances over 150 MJ/h input ........................................................................................1500
k - From a mechanical air inlet, including a spa blower ......................................................... 1500
n - Vertically below an openable window, non-mechanical air
inlet or any other opening into a building, with the exception of ................................. See table
sub-floor ventilation............................................................................................................. below
T = Flue terminal M = Gas meter Shading indicates prohibited
I = Mechanical air inlet P = Electricity meter or fuse box areas for flue terminals