Top Vent - Vertical Termination

Venting with 3 elbows (NG)

V1 Minimum

H1 Maximum

V2

V1 + V2 Minimum

90 Elbow

0 ft.

305 mm

*

*

 

 

 

 

 

 

1/2 ft.

152 mm

2 ft.

610 mm

*

*

 

 

 

 

 

 

1-1/2 ft.

457 mm

3 ft.

914 mm

*

*

 

 

 

 

 

 

2-1/2 ft.

762 mm

5 ft.

1.5 m

*

*

 

 

 

 

 

 

3-1/2 ft.

1.1 m

7 ft.

2.1 m

*

*

 

 

 

 

 

 

4-1/2 ft.

1.4 m

15 ft.

4.6 m

*

*

 

 

 

 

 

 

H MAX. =15 ft. (4.6 m)

V1+ V2 + H1 MAX. = 40 ft. (12.2 m)

* No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 cannot exceed 40 ft. (12.2 m)

Top Vent - Vertical Termination

Venting with 3 elbows (Propane)

V1 Minimum

H1 Maximum

V2

V1 + V2 Minimum

90 Elbow

Not Allowed

*

*

 

 

 

 

 

 

1/2 ft.

152 mm

1 ft.

305 mm

*

*

 

 

 

 

 

 

1-1/2 ft.

457 mm

3 ft.

914 mm

*

*

 

 

 

 

 

 

2-1/2 ft.

762 mm

5 ft.

1.5 m

*

*

 

 

 

 

 

 

3-1/2 ft.

1.1 m

7 ft.

2.1 m

*

*

4-1/2 ft.

1.4 m

15 ft.

4.6 m

*

*

 

 

 

 

 

 

H MAX. =15 ft. (4.6 m)

V1+ V2 + H1 MAX. = 40 ft. (12.2 m)

* No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 cannot exceed 40 ft. (12.2 m)

Note: Use SLP Series components only.

V2

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 5.3).

H1

H2

V1

INSTALLED

HORIZONTALLY

Figure 7.10

Quadra-FireQV32B-A, QV36B-A2014-900 Rev. U • 1/12

29

Page 29
Image 29
Hearth and Home Technologies QV36B-A, QV32B-A owner manual Top Vent Vertical Termination Venting with 3 elbows NG