Heat & Glo LifeStyle 6000TRS-CD C. Flue Termination, If Exterior Walls Are Finished With Vinyl

Models: 6000TRS-CD

1 42
Download 42 pages 3.32 Kb
Page 24
Image 24
C. Flue Termination

24

If the area above the ceiling is NOT an attic, position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole.

IF EXTERIOR WALLS ARE FINISHED WITH VINYL JOIST

CEILING

NAILS (4 REQUIRED)

CEILING FIRESTOP

FIGURE 20. Ceiling Firestop (Ceiling Side)

If the area above the ceiling IS an attic, position and secure the firestop on top of the previously framed hole.

NAILS (4 REQUIRED)

RAFTER

 

CEILING

 

CEILING FIRESTOP

 

 

 

FIGURE 21. Attic Firestop

 

C. Flue Termination

CAUTION:

IF EXTERIOR WALLS ARE FINISHED WITH VINYL

 

SIDING, IT IS NECESSARY TO INSTALL THE VINYL

 

PROTECTOR KIT (VPK-DV) TO THE TOP OF THE

 

EXTERIOR FIRESTOP FOR ALL ROUND

 

TERMINATION CAPS.

 

For Horizontal Terminations using the DVP-TRAP

 

To attach and secure the termination to the last section of

 

horizontal flue:

 

• The rear flue heat shield MUST be placed 2.54 cm above

 

the top of the flue between the wall shield and the base

 

of the termination cap.

 

• One section of the heat shield is attached to the wall

 

shield. The other is attached to the termination cap in

 

the same manner (see Figure 22).