FOLLOW NATIONAL REGULATIONS

 

!

WARNING:

 

 

FOLLOW NATIONAL REGULATIONS

 

 

AND CODES OF PRACTICE FOR

 

 

MINIMUM CLEARANCES FROM GAS

 

 

TERMINALS, AND PLACEMENT OF GAS

 

 

TERMINAL.

NOTE

This also pertains to vertical flue systems installed

 

on the outside of the building.

TERMINATION CAP

TERMINATION

CAP

50.8 cm

VERTICAL

WALL

LOWEST

DISCHARGE

OPENING

X

30.5 cm

AND CODES OF PRACTICE FOR ROOF PITCH

IS X/ 30.5 cm

H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

Roof Pitch

H (min.) cm

flat to 6/12

30.5*

6/12 to 7/12

38*

over 7/12 to 8/12

45.75*

over 8/12 to 9/12

61*

over 9/12 to 10/12

76.25*

over 10/12 to 11/12

99

over 11/12 to 12/12

122

over 12/12 to 14/12

152.5

over 14/12 to 16/12

183

over 16/12 to 18/12

213.5

over 18/12 to 20/12

228.75

over 20/12 to 21/12

244

* 91.4 cm minimum in snow regions

Figure 24. Minimum Height from Roof to Lowest

Discharge Opening

27