STRAIGHT UP
VERTICAL VENTING
V (FT.)
40' MAX. (12.4 M)
CAP
V
DIAMETER |
NOTE: On vertical venting configurations install the vertical baffle found in your manual bag per the flue restrictor instructions in this section.
Figure 6.
Straight Up Vertical Venting
Flue Restrictor Instructions
1.Locate the flue restrictors inside the unit to the left of the control panel. There is one each of the
Vent Run | |||
Vertical | |||
|
| ||
NG | |||
LP | 2” |
Figure 8. Flue Restrictor |
Pilot Shield Adjustment
When venting this unit with high vertical (8 feet or more) Í with very little horizontal the pilot shield will need to be bent down in the closed position as shown in Figure 9.
PILOT |
BRACKET |
PILOT SHIELD |
PILOT SHIELD SHOULD BE |
CLOSED AND TOUCHING |
THE PILOT BRACKET |
Figure 9 |
Note: When venting this unit with long horizontal runs Í and/or multiple elbows, the pilot shield will need to be in the opened position as in Figure 10.
2.See Figure 8 for restrictor installation. Insert each restric- tor in one of the 3” exhaust collars as shown.
FLUE |
RESTRICTOR |
FLUE |
RESTRICTOR |
Figure 7 |
PILOT SHIELD |
BEND PILOT SHIELD UP 3/8” |
TO ALLOW AIR FLOW TO |
FEED THE PILOT FLAME |
Figure 10 |
14 | Heat & Glo • GEM42 • |