5-7. Electrical Service Guide
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommendations are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
| 60 Hz Single Phase | ||
|
|
| |
Input Voltage (V) | 230 Volts AC | 115 Volts AC | |
|
|
| |
Input Amperes (A) At Rated Output | 24 |
| |
|
|
| |
Max Recommended Standard Fuse Rating In Amperes 1 |
| A 20 ampere | |
30 | individual branch | ||
Normal Operating Fuses 3 |
| circuit | |
35 | protected by | ||
|
| ||
Min Input Conductor Size In AWG 4 | 14 | ||
or circuit breaker | |||
|
| is required. | |
Max Recommended Input Conductor Length In Feet (Meters) | 53 | ||
See Section | |||
(16) | |||
| |||
|
|
| |
Min Grounding Conductor Size In AWG 4 | 14 |
| |
Reference: 2008 National Electrical Code (NEC) (including article 630) |
|
|
1If a circuit breaker is used in place of a fuse, choose a circuit breaker with
2
3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and above).
4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
5-8. Extension Cord Data (Use Shortest Cord Possible)
.When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
| Input Power |
|
|
|
Input Voltage | Phase | Hertz | Conductor Size | Max. Cord Length |
|
|
|
|
|
115 V | 1 | 60 | 14 AWG | 25 ft (8 m) |
|
|
|
|
|
115 V | 1 | 60 | 12 AWG | 55 ft (17 m) |
|
|
|
|
|
115 V | 1 | 60 | 10 AWG | 100 ft (30 m) |
|
|
|
|
|
230 V | 1 | 60 | 14 AWG | 53 ft (16 m) |
|
|
|
|
|