BUILDING NETWORK ADAPTER BNA-1C/2CS/2DN

For each channel the required termination setting can be adjusted individually.

At the rear side of the device, a pictogram (Figure 5-2) symbolizes the different possible bus terminations.

Figure 5-2

 

normal

XD505 compatible bus termination for

 

C- /S- /FS90-Bus connections

 

It is required to use this switch position

 

for S-Bus and FS90-Bus in any case. For

 

C-Bus connections, this position must

 

be used when at least one XL IRC or

 

XL MC is connected to the C-Bus.

 

 

 

 

 

XD508 compatible; bus termination

 

 

 

 

 

disabled

 

 

 

 

 

XD508 compatible switch position for

 

 

 

 

 

C-Busses equipped only with XL500

 

 

 

 

 

family controllers with bus termination

 

 

 

 

 

disabled. This switch position must be

 

 

 

 

 

used if the BNA device is installed in

 

 

 

 

 

the middle of such a C-Bus.

 

 

 

 

 

 