BUILDING NETWORK ADAPTER BNA-1C/2CS/2DN
XD508 compatible; bus termination enabled
XD508 compatible switch position for
5.4L1 Bus Termination
This section applies to BNA 2DN devices only.
The required L1 bus EOLRs (End of Line Resistors) can be connected externally onto each CH1 / CH2 connector.
When the L1 bus uses 18 gage, twisted pair, non- shielded wire, the ends of the line should be terminated with a 62 Ω ±10% 0,5 W carbon resistor between each wire and ground.
When the L1 bus uses 24 gage, dedicated solid copper pair, standard balanced telephone cable, the ends of the line should be terminated with a 100 Ω ±5% 0,5 W carbon resistor between each wire and ground.
For further information regarding L1 bus termination, please refer to Honeywell DeltaNet R7044 EXCEL PLUS CONTROLLER Application Guide
22 |