Hoshizaki HUR96A(-D) Timing Chart, Time, Defrost Thermistor, Cabinet Thermistor, Compressor

Models: HWR68A(-D) HUR40A(-D) HUR68A(-D) HUR96A(-D) HWR40A(-D)

1 64
Download 64 pages 59.88 Kb
Page 16
Image 16
8 min.

 

 

 

 

 

Freezers – Continuous

b)

Defrost Termination Temperature

 

 

 

Timing Chart

 

Defrost Thermistor

 

 

 

 

No meaning

 

 

 

 

Setpoint + Differential (+)

 

 

 

 

Cabinet Thermistor

 

 

 

 

Setpoint + Differential (--)

 

 

 

 

 

 

2 min.

 

 

 

 

 

Operating

 

 

ON

 

(Min. ON)

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

OFF

2 min.

2 min.

5 min.

 

 

 

 

 

 

(Start Delay)

(Min. OFF)

(Drain Delay)

 

 

ON

Mode

 

 

 

 

 

 

 

Condenser Fan

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

16

ON

 

 

 

 

 

Evaporator Fan(s)

 

 

 

 

 

 

OFF

 

 

 

5 min.

 

 

 

 

 

 

 

 

ON

 

 

 

(Fan Delay)

 

 

 

 

< 60 min.

 

 

 

Defrost Heater

 

 

 

 

 

OFF

 

 

(Max. Defrost Duration)

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

Defrost Indicator

 

 

 

8 min.

 

 

OFF

 

 

 

(Display Delay)

 

 

ON

 

 

 

 

 

 

Frame Heater(s)

 

 

 

 

 

 

OFF

 

 

 

 

 

Time 6 hours

6 hours

(Defrost Start - Adjustable)

Power ON

Page 16
Image 16
Hoshizaki HUR96A(-D) Timing Chart, Time, Defrost Thermistor, Cabinet Thermistor, Compressor, Condenser Fan, Defrost Heater