Hoshizaki HUR40A(-D), HWR40A(-D), HUR96A(-D), HUR68A(-D) c Setpoint Temperature Differential F2

Models: HWR68A(-D) HUR40A(-D) HUR68A(-D) HUR96A(-D) HWR40A(-D)

1 64
Download 64 pages 59.88 Kb
Page 28
Image 28

3)Press the c)Setpoint Temperature Differential (F2) unmarked, blank button to display the current setting. Press the Manual background up or

Manual background down button to increase or decrease the defrost termination temperature.

Note: The defrost termination temperatures can be adjusted within the following ranges:

Refrigerator: 59 to 68°F (15 to 20°C) in one degree increments

Freezer: 41 to 68°F (5 to 20°C) in one degree increments

4)Press the Manual background unmarked, blank button to save the setting.

5)Press the MANUAL DEFROST button to return to the menu screen. Press and hold

both the Manual background button and the Manual background unmarked, blank button for 5 seconds to exit the setting mode and return to the temperature display.

6)If a jumper was present between connector K151 pins 7 and 8, reconnect it after all setting and diagnostic work is complete.

c)Setpoint Temperature Differential (F2)

To change the differential, follow the steps below.

1)Make sure the jumper is removed between connector K151 pins 7 and 8 on the control board. Otherwise you will not be able to access this setting. For details, see "D.1. Gaining Access to Settings and Diagnostics."

2)Press and hold both the Manual background button and the Manual background unmarked, blank button for 5 seconds. "F0" should appear in the display window. Press the MANUAL DEFROST button until "F2" appears in the display window.

3)Press the Manual background unmarked, blank button to display the current + setting (the decimal

between the digits is not shown). Press the Manual background up or Manual background down button to increase or decrease the + (plus) differential in .9°F increments.

Note:

Both the + and - values can be adjusted between 0.0 and 6.3°F in .9°F increments (0.0 to 3.5°C in .5°C increments).

You cannot set both + and - to 0.0.

4)Press the Manual background unmarked, blank button to save the + setting and move to the - (minus) differential setting.

5)Press the Manual background up or Manual background down button to increase or decrease the - (minus) differential in

.9F increments. Note:

Both the + and - values can be adjusted between 0.0 and 6.3°F in .9°F increments (0.0 to 3.5°C in .5°C increments).

You cannot set both + and - to 0.0.

6)Press the Manual background unmarked, blank button to save the - (minus) setting. The - (minus) sign will turn off and the display will change to the + (plus) differential setting.

7)Press the MANUAL DEFROST button to return to the menu screen. Press and hold

both the Manual background button and the Manual background unmarked, blank button for 5 seconds to exit the setting mode and return to the temperature display.

8)If a jumper was present between connector K151 pins 7 and 8, reconnect it after all setting and diagnostic work is complete.

28