f. Defrost Temperature Sensor Malfunction Alarm (E8)
If input from the defrost thermistor is below the defrost open circuit detection point (equivalent to
Note:
•If this alarm appears, first make sure that the sensor is properly connected.
•A short circuit will not be detected during the first hour after power is turned on. However, a short circuit can be detected immediately by turning on the power
while pressing the button. In this case, "E8" will be displayed immediately if a short circuit is detected.
• A short circuit will not be detected during defrost or fan delay.
Reset Options
The alarm automatically resets when one of the following conditions is met:
•The input from the defrost thermistor exceeds the open circuit detection point (equivalent to
•The input from the defrost thermistor drops below the short circuit detection point (equivalent to 122°F (50°C)).
•A functioning defrost thermistor (orange) is installed.
Possible Causes
• Trouble with the defrost thermistor (orange).
39