III. Service Diagnosis

A. Alarm Codes

If an error occurs, the alarm code and cabinet temperature are displayed in 1-second intervals. See the table below for a general description of the problem, then see the rest of this section for detailed instructions.

Alarm Signals

Alarm Code

Problem

Notes

 

High Temperature Alarm

When temperature returns to setpoint range,

 

 

alarm code "E1" will clear.

 

Cabinet temperature has exceeded set

 

E1

temperature by 14.4°F (10°C) for more than

The value of x can be changed under F3 on the

 

x hours. The default value of x is "2" (2 hours).

Settings and Diagnostics Menu.

 

 

(0=No delay; 1=1 hour; 2=2 hours; 3=3 hours)

 

 

 

 

Low Temperature Alarm

When temperature returns to setpoint range,

 

 

alarm code "E2" will clear.

 

Cabinet temperature has remained below

 

E2

setpoint by 9°F (5°C) for more than y hours.

The value of y can be changed under F4 on the

 

The default value of y is "1" (1 hour).

Settings and Diagnostics Menu.

 

 

(0=No delay; 1=hour)

 

 

 

 

Defrost Alarm

E3 may alternate with "dF" instead of the

E3

 

temperature.

Defrost has taken longer than 1 hour. Control

 

 

 

 

board has terminated defrost.

 

 

 

 

 

High Pressure Alarm

Clean filter if necessary. Allow time for

 

 

pressure switch to react, then turn power off

 

Compressor discharge pressure is outside

and back on again to reset.

E4

normal operating range. Pressure switch has

 

 

been triggered 5 or more times in 1 hour.

If switch trips 5 times in 1 hour, and the

 

Condenser filter may need cleaning.

above steps do not clear alarm code, see the

 

 

procedure contained in this section.

 

Clogged Filter Alarm

Clean filter. Allow time for sensor to react, then

 

 

turn power off and back on again to reset.

E7

Condenser temperature is outside of normal

 

 

operating range. Condenser filter needs

 

 

cleaning.

 

 

Defrost Temperature Sensor Malfunction Alarm

After replacing sensor, alarm will reset.

E8

 

 

 

Defrost temperature sensor has failed.

 

 

Clogged Filter Sensor Malfunction Alarm

After replacing sensor, alarm will reset.

E9

 

 

 

Clogged filter sensor has failed.

 

 

EEPROM Write Error Alarm

After replacing the control board, alarm will

EA

 

reset.

 

Control board is defective.

 

 

EEPROM Verification or Read Error Alarm

After replacing the control board, alarm will

ED

 

reset.

 

Control board is defective.

 