Hoshizaki KM-630MAH, KM-630MWH, KM-630MRH service manual Evaporator Is Frozen Up

Models: KM-630MAH KM-630MRH KM-630MWH

1 67
Download 67 pages 19.6 Kb
Page 44
Image 44

2. EVAPORATOR IS FROZEN UP

PROBLEM

 

POSSIBLE CAUSE

 

REMEDY

[1] Freeze cycle

 

a) Float Switch

1.

Leads short-circuit or

1.

Check and replace.

time is too

 

 

 

 

 

defective switch.

 

 

 

 

long.

 

 

2.

Float does not move freely.

2.

Clean or replace.

 

 

b) Water Solenoid

1.

Diaphragm does not close.

1.

Check for water leaks

 

 

Valve

 

 

 

 

 

with icemaker off.

 

 

c) Controller Board

 

 

1. Defective.

1.

See “II.2[e] CHECKING

 

 

 

 

 

 

 

 

CONTROLLER BOARD.”

[2] All ice formed

 

a) Evaporator

1.

Scaled up.

1.

Clean.

 

 

on Evaporator

 

b) Water Supply Line

1.

Water pressure too low.

1.

Check and get

does not fall

 

 

 

 

 

 

 

recommended pressure.

into bin in

 

c) Water Solenoid

1.

Dirty mesh filter or orifice.

1.

Clean.

harvest cycle.

 

Valve

2.

Diaphragm does not close.

2.

Check for water leaks

 

 

 

 

 

 

 

 

with icemaker off.

 

 

d) Ambient and/or

1.

Too cool.

1.

Increase temperature.

 

 

water temperature

 

 

 

 

 

 

 

 

 

 

e) Line Valve

1.

Continues to open in

1.

Check operation in

 

 

 

 

 

 

harvest cycle.

 

harvest cycle and replace.

 

 

f) Thermistor

1.

Out of position or loose

1. See “V. 11. REMOVAL

 

 

 

 

 

 

attachment..

 

AND REPLACEMENT OF

 

 

 

 

 

 

 

 

THERMISTOR.”

 

 

g) Controller Board

1.

Defrost Timer is set too

1.

Adjust longer, referring

 

 

 

 

 

 

 

short.

 

to “II. 2. [d] CONTROLS

 

 

 

 

 

 

 

 

AND ADJUSTMENT, 2)

 

 

 

 

 

 

 

 

Defrost Timer.”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Defective.

2.

See “II. 2.[e] CHECKING

 

 

 

 

 

 

 

 

CONTROLLER BOARD.”

[3] Others

 

a) Spray Tubes

 

 

1. Clogged.

1. Clean.

 

 

 

 

2.

Out of position.

2.

Place in position.

 

 

 

b) Water System

1.

Dirty.

1.

Clean.

 

 

c) Refrigerant

 

 

1. Undercharged.

1.

Check for leaks and

 

 

 

 

 

 

 

 

recharge.

 

 

d) Expansion Valve

1.

Bulb out of position or

1.

Place in position.

 

 

 

 

 

 

loose attachment.

 

 

 

 

 

 

 

 

 

2. Defective.

2.

Replace.

 

 

e) Hot Gas Solenoid

 

 

1. Coil winding opened.

1. Replace.

 

 

Valve

2.

Plunger does not move.

2. Replace.

 

 

 

 

3.

Wiring to Hot Gas Valve.

3.

Check for loose

 

 

 

 

 

 

 

 

connection or open, and

 

 

 

 

 

 

 

 

replace.

 

 

f) Water Supply Line

1.

Too small; requires 3/8”

1.

Increase Water Line size.

 

 

 

 

 

 

OD line dedicated per

 

 

 

 

 

 

 

 

 

 

machine.

 

 

 

 

 

 

g) Water Filter (if

1.

Flow rate too small.

1.

Replace with filter with

 

 

installed)

 

 

 

 

 

larger flow rate.

 

 

 

 

 

 

 

 

 

 

 

44

Page 44
Image 44
Hoshizaki KM-630MAH, KM-630MWH, KM-630MRH service manual Evaporator Is Frozen Up