Hoshizaki KMD-410MWH manual KMD-410MAH, 410MWH, Drain Cycle

Models: KMD-410MWH KMD-410MAH

1 65
Download 65 pages 49.57 Kb
Page 11
Image 11
KMD-410MAH, 410MWH

KMD-410MAH, 410MWH

7

xMaximum harvest water valve time: 6 minutes (HWV time is 6 minutes of the length of harvest minus 0, 10, 30, or 50 sec. (S1 dip switch

7 & 8), whichever is shorter. PM energizes and runs for the last 0, 10, 30, or 50 sec. of harvest.)

xMaximum harvest time: 20 minutes

0, 0,30, or 50 sec

“H” board will have 5 second delay

HWV energized COMP energized HGV energized HWV continues FWV de-energized DV de-energized

xMinimum freeze time: 5 minutes

xMaximum freeze time: freeze time setting xLower float switch used to initiate water Tank refill (1 refill for KMD-410) xUpper float switch used to terminate water tank refill (1 minute maximum fill time)

COMP continues PM continues FWV energized/

de-energized for refill only

FMS energized HGV de-energized

4. Drain Cycle

Factory set for every 10th cycle (S1 dip Switch 5 & 6)

Pump motor stops for 2 sec. and then runs for 10/20 sec.

(S1 dip switch 3 & 4)

PM de-energizes 0/2 sec., energizes for 10/20 sec.

COMP continues DV energized/ HGV energized FMS de-energized

Legend:

COMP - compressor DV – drain valve

FMS self-contained fan motor FWV – fill water valve

HGV – hot gas valve HWV – harvest water valve

LF/S – lower float switch contacts PM – pump motor

UF/S – upper float switch contacts

Page 11
Image 11
Hoshizaki KMD-410MWH manual KMD-410MAH, 410MWH, Drain Cycle