Thermal and air flow performance

Maximum thermal and air flow performance

Specifications

parameters

 

 

 

Air temperature—inlet to rack-mounted components

25ºC (68ºF)

 

 

Chilled water temperature

7º–10°C (45º–50°F)

 

 

Total rack-mounted component air flow

2,600 cfm or less at 0 or more pressure drop

 

across the rack-mounted components

 

 

Chilled water flow rate

21 gal/min

 

 

Chilled water pressure differential at flow needed to

2.0 bar delta pressure

meet thermal specifications

 

 

 

Heat lost to room

approximately 10% maximum depending on

 

the MCS settings and room temperature

 

 

Heat transferred to cooling fluid

35 kW maximum

 

 

Environmental specifications

Features

Specifications

 

 

Operating temperature

5ºC to 35ºC (41ºF to 95ºF)

 

 

Non-operating temperature

0ºC to 60ºC (32ºF to 140ºF)

 

 

Transit temperature

-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours

 

 

Storage temperature

-20ºC to 60ºC (-4ºF to 140ºF)

 

 

Operating humidity

20 to 80% relative humidity (non-condensing)

 

 

Non-operating humidity

5 to 95% relative humidity (non-condensing)

 

 

Operating altitude

-76.2 to 3,048 m (-250 to 10,000 ft)

 

 

Non-operating altitude

-76.2 to 9,144 m (-250 to 30,000 ft)

 

 

HP 10642 G2 Rack specifications

U height

Width

Depth

Dynamic load (gross)

Static load

 

 

 

 

 

42U

600 mm

1,000 mm

907.18 kg (2,000 lb)

907.18 kg (2,000

 

(23.82 in)

(39.37 in)

 

lb)

 

 

 

 

 

Specifications 143

Page 143
Image 143