Controller application setting parameters
  | Para-  | 
  | Controller  | 
  | Min.  | Max.  | Factory  | Actual  | |
Setting and   | meter  | 
  | application no.  | 
  | |||||
  | 
  | value  | value  | setting  | setting  | ||||
  | codes  | 1  | 2  | 3  | 4  | ||||
  | 
  | 
  | 
  | 
  | |||||
  | 
  | 
  | 
  | 
  | 
  | ||||
Temperature controller, Temperature  | 
  | 
  | 
  | 
  | 
  | 50oC  | 3oC  | 
  | |
Thermostat | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Differential1)  | r01  | 
  | 
  | 
  | 
  | 0.1 K  | 20 K  | 2 K  | 
  | 
Max. limitation of set temperature  | r02  | 
  | 
  | 
  | 
  | 50oC  | 50oC  | 
  | |
Min. limitation of set temperature  | r03  | 
  | 
  | 
  | 
  | 49oC  | 
  | ||
Adjustment of temperature indication  | r04  | 
  | 
  | 
  | 
  | 20 K  | 0.0 K  | 
  | |
Temperature unit (°C/°F)  | r05  | 
  | 
  | 
  | 
  | 
  | 
  | oC  | 
  | 
Alarm | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Upper deviation (above temp. setting + differential 2)  | A01  | 
  | 
  | 
  | 
  | 0 K  | 50 K  | 5 K  | 
  | 
Lower deviation (below temp. setting 2)  | A02  | 
  | 
  | 
  | 
  | 0 K  | 50 K  | 5 K  | 
  | 
Temperature alarm delay  | A03  | 
  | 
  | 
  | 
  | 0 min  | 90 min  | 30 min  | 
  | 
Door alarm delay  | A04  | 
  | 
  | 
  | 
  | 0 min  | 60 min  | 30 min  | 
  | 
Compressor  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Min.   | c01  | 
  | 
  | 
  | 
  | 0 min  | 15 min  | 0 min  | 
  | 
Min.   | c02  | 
  | 
  | 
  | 
  | 0 min  | 15 min  | 0 min  | 
  | 
c03  | 
  | 
  | 
  | 
  | 0 %  | 100 %  | 0 %  | 
  | |
Defrost | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Defrost method (EL/GAS)  | d01  | 
  | 
  | 
  | 
  | 
  | 
  | EL  | 
  | 
Defrost stop temperature  | d02  | 
  | 
  | 
  | 
  | 0oC  | 25oC  | 6oC  | 
  | 
Interval between defrost starts  | d03  | 
  | 
  | 
  | 
  | OFF | 48 hour  | 8 hour  | 
  | 
Max. defrost duration  | d04  | 
  | 
  | 
  | 
  | 0 min  | 180 min  | 45 min  | 
  | 
Time staggening on defrost   | d05  | 
  | 
  | 
  | 
  | 0 min  | 60 min  | 0 min  | 
  | 
d06  | 
  | 
  | 
  | 
  | 0 min  | 20 min  | 0 min  | 
  | |
Fan start delay after defrost  | d07  | 
  | 
  | 
  | 
  | 0 min  | 20 min  | 0 min  | 
  | 
Fan start temperature  | d08  | 
  | 
  | 
  | 
  | 0oC  | 
  | ||
Fan   | d09  | 
  | 
  | 
  | 
  | 
  | 
  | yes  | 
  | 
Defrost sensor (yes/no)  | d10  | 
  | 
  | 
  | 
  | 
  | 
  | yes  | 
  | 
Temperature alarm delay after defrost  | d11  | 
  | 
  | 
  | 
  | 0 min  | 199 min  | 90 min  | 
  | 
Fan  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Fan stop on compressor   | F01  | 
  | 
  | 
  | 
  | 
  | 
  | no  | 
  | 
Fan stop delay  | F02  | 
  | 
  | 
  | 
  | 0 min  | 15 min  | 0 min  | 
  | 
Miscellaneous | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Delay of output signal cancellation after   | o01  | 
  | 
  | 
  | 
  | 2 s  | 120 s  | 2 s  | 
  | 
Digital input signals 4)  | o02  | 
  | 
  | 
  | 
  | 
  | 
  | 0  | 
  | 
(0 = not used, 1 = door alarm, 2 = defrost, 3 = bus)  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Real time clock (if fitted) | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Six start times for defrost  | t01→ t06  | 
  | 
  | 
  | 
  | 0  | 23  | OFF  | 
  | 
All can be cut out by setting on OFF  | 
  | 
  | 
  | 
  | 
  | ||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Hour setting  | t07  | 
  | 
  | 
  | 
  | 0 hour  | 23 hour  | 0 hour  | 
  | 
Minute setting  | t08  | 
  | 
  | 
  | 
  | 0 min  | 59 min  | 0 min  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Fault code display | 
  | Alarm code display | 
Fault in controller  | E 1  | High temperature alarm  | 
Disconnected room sensor  | E 2  | Low temperature alarm  | 
E 3  | Door alarm  | |
Disconnected defrost sensor  | E 4  | Status code display | 
E 5  | ||
  | 
  | |
  | 
  | |
  | 
  | 
  | 
A1 A 2 A 4
S2 S 3 S 4
1) The compressor relay closes when the room temperature exceeds the setting value and differential.
2) Alarm is released and sensor failure is indicated, if the room temperature reaches 5°C or more outside the setting range
3)The frequency is measured after approx. three days and nights operation after start of the plant (72 cyclings)
otherwise:
4) Function possibilities with SPDT contact, connected to the terminals 3 and 4 are the following:
Door alarm: If SPST is cut out, alarm signalling starts and the fan is stopped, cf. A04 or F02.
Defrost: If SPST is cut in, defrost starts. (However, if d03 is not OFF, defrost will during contact break down start with the programmed time intervalles).
Bus: With installed communication card, the position of the SPST contacts will be registered in the BUS system.