hussman SCSS-SL manual Controller application setting parameters

Models: SCSS SCSS-SL

1 24
Download 24 pages 45.19 Kb
Page 11
Image 11
Controller application setting parameters

Rev. 0108

Controller application setting parameters

 

Para-

 

Controller

 

Min.

Max.

Factory

Actual

Setting and read-off parameters

meter

 

application no.

 

 

 

value

value

setting

setting

 

codes

1

2

3

4

 

 

 

 

 

 

 

 

 

 

 

Temperature controller, Temperature

 

 

 

 

 

-60oC

50oC

3oC

 

Thermostat

 

 

 

 

 

 

 

 

 

Differential1)

r01

 

 

 

 

0.1 K

20 K

2 K

 

Max. limitation of set temperature

r02

 

 

 

 

-59oC

50oC

50oC

 

Min. limitation of set temperature

r03

 

 

 

 

-60oC

49oC

-60oC

 

Adjustment of temperature indication

r04

 

 

 

 

-20 K

20 K

0.0 K

 

Temperature unit (°C/°F)

r05

 

 

 

 

 

 

oC

 

Alarm

 

 

 

 

 

 

 

 

 

Upper deviation (above temp. setting + differential 2)

A01

 

 

 

 

0 K

50 K

5 K

 

Lower deviation (below temp. setting 2)

A02

 

 

 

 

0 K

50 K

5 K

 

Temperature alarm delay

A03

 

 

 

 

0 min

90 min

30 min

 

Door alarm delay

A04

 

 

 

 

0 min

60 min

30 min

 

Compressor

 

 

 

 

 

 

 

 

 

Min. ON-time

c01

 

 

 

 

0 min

15 min

0 min

 

Min. OFF-time

c02

 

 

 

 

0 min

15 min

0 min

 

Cut-in frequency on sensor fault 3)

c03

 

 

 

 

0 %

100 %

0 %

 

Defrost

 

 

 

 

 

 

 

 

 

Defrost method (EL/GAS)

d01

 

 

 

 

 

 

EL

 

Defrost stop temperature

d02

 

 

 

 

0oC

25oC

6oC

 

Interval between defrost starts

d03

 

 

 

 

OFF

48 hour

8 hour

 

Max. defrost duration

d04

 

 

 

 

0 min

180 min

45 min

 

Time staggening on defrost cut-ins at start-up

d05

 

 

 

 

0 min

60 min

0 min

 

Drip-off time

d06

 

 

 

 

0 min

20 min

0 min

 

Fan start delay after defrost

d07

 

 

 

 

0 min

20 min

0 min

 

Fan start temperature

d08

 

 

 

 

-15oC

0oC

-5oC

 

Fan cut-in during defrost (yes/no)

d09

 

 

 

 

 

 

yes

 

Defrost sensor (yes/no)

d10

 

 

 

 

 

 

yes

 

Temperature alarm delay after defrost

d11

 

 

 

 

0 min

199 min

90 min

 

Fan

 

 

 

 

 

 

 

 

 

Fan stop on compressor cut-out (yes/no)

F01

 

 

 

 

 

 

no

 

Fan stop delay

F02

 

 

 

 

0 min

15 min

0 min

 

Miscellaneous

 

 

 

 

 

 

 

 

 

Delay of output signal cancellation after start-up

o01

 

 

 

 

2 s

120 s

2 s

 

Digital input signals 4)

o02

 

 

 

 

 

 

0

 

(0 = not used, 1 = door alarm, 2 = defrost, 3 = bus)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Real time clock (if fitted)

 

 

 

 

 

 

 

 

 

Six start times for defrost

t01t06

 

 

 

 

0

23

OFF

 

All can be cut out by setting on OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hour setting

t07

 

 

 

 

0 hour

23 hour

0 hour

 

Minute setting

t08

 

 

 

 

0 min

59 min

0 min

 

 

 

 

 

 

 

 

 

 

 

Fault code display

 

Alarm code display

Fault in controller

E 1

High temperature alarm

Disconnected room sensor

E 2

Low temperature alarm

Short-circuited room sensor

E 3

Door alarm

Disconnected defrost sensor

E 4

Status code display

Short-circuited defrost sensor

E 5

ON-time

 

 

OFF-time

 

 

Drip-off time

 

 

 

A1 A 2 A 4

S2 S 3 S 4

1) The compressor relay closes when the room temperature exceeds the setting value and differential.

2) Alarm is released and sensor failure is indicated, if the room temperature reaches 5°C or more outside the setting range

–60°to +50°C.

3)The frequency is measured after approx. three days and nights operation after start of the plant (72 cyclings)

otherwise:

ON-time = c03 20: 100 minutes

OFF-time interval 20 minus ON-time per minute

4) Function possibilities with SPDT contact, connected to the terminals 3 and 4 are the following:

Door alarm: If SPST is cut out, alarm signalling starts and the fan is stopped, cf. A04 or F02.

Defrost: If SPST is cut in, defrost starts. (However, if d03 is not OFF, defrost will during contact break down start with the programmed time intervalles).

Bus: With installed communication card, the position of the SPST contacts will be registered in the BUS system.

11