Rev. 0108

 

Refrigeration

REFRIGERANT TYPE

THERMOSTATIC EXPANSION VALVE LOCATION

The standard refrigerant will be R-22 unless otherwise specified on the customer order. Check the serial plate on the case for information.

REFRIGERATION LINES

LIQUID SUCTION

3/8" O.D.

5/8" O.D.

NOTE: The standard coil is piped at 5/8" (suction); however, the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be

5/8", 7/8", or 11/8". Refer to the particular case you are hooking up.

This device is located on the same side as the refrigera- tion stub. A Sporlan balanced port expansion valve model is furnished as standard equipment, unless otherwise speci- fied by customer.

EXPANSION VALVE ADJUSTMENT

Expansion valves must be adjusted to fully feed the evapo- rator. Before attempting any adjustments, make sure the evaporator is either clear or very lightly covered with frost, and that the fixture is within 10°F of its expected operat- ing temperature.

MEASURING THE OPERATING SUPERHEAT

Refrigerant lines should be sized as shown on the refrig- eration legend furnished by the store.

Install P-traps (oil traps) at the base of all suction line ver- tical risers.

Pressure drop can rob the system of capacity.To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.

CONTROL SETTINGS

See the “Case Specs” section of this guidebook for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product tempera- tures. For all multiplexing, defrost should be time termi- nated. Defrost times should as directed in the Case Speci- fications section of this guide.The number of defrosts per day should never change.The duration of the defrost cycle may be adjusted to meet conditions present at your loca- tion.

0°F / -18°C or less air temperature.Adequate performance is assured by the desired condition of the product in case.

ACCESS TO TX VALVES & DRAIN LINES

MECHANICAL - Remove product from end of case. Remove product racks.Remove refrigeration and drain access panels (labeled).TX valve (mechanical only) and drain are located under each access panel at end of the case.

ELECTRONIC - The Electronic Expansion valve master and slave cylinder(s) are located within the electrical access panel(s).

ELECTRONIC EXPANSION VALVE (OPTIONAL)

A wide variety of electronic expansion valves and case controllers can be utilized. Please refer to EEV and con- troller manufacturers information sheet. Sensors for elec- tronic expansion valves will be installed on the coil inlet, coil outlet, and in the discharge air. (Some supermarkets require a 4th sensor in the return air). Case controllers will be located in the electrical raceway or under the case

1.Determine the suction pressure with an accurate pressure gauge at the evaporator outlet.

2.From a refrigerant pressure temperature chart, determine the saturation temperature at the observed suction pressure.

3.Measure the temperature of the suction gas at the thermostatic remote bulb location.

4.Subtract the saturation temperature obtained in step No.2 from the temperature measured in step No.3.

3. The difference is superheat.

5. Set the superheat for 5°F - 7°F.

Multiplexing - Piping of merchandisers operating on the same refrigeration system may be run from merchandiser to merchandiser through the end frame saddles provided for this purpose. DO NOT RUN REFRIGERANT

LINESTHROUGH MERCHANDISERSTHATARE

NOTTHE SAME REFRIGERATION SYSTEM as this may result in poor refrigeration control and compressor failure.

Line Sizing - Refrigerant lines should be sized as shown on the refrigeration legend that is furnished for the store (not furnished by Hussmann). If a legend has not been furnished, refer to the Hussmann Application Engineering Manual for guidance.

Oil Traps - P-traps (oil traps) must be installed at the base of all suction line vertical risers.

Pressure Drop - Pressure drop can rob the system of capacity. To keep the pressure drop to a minimum, keep the refrigerant line run as short as possible using a minimum number of elbows.Where elbows are required, use long radius elbows only.

Insulation -The suction and liquid lines should be clamped or taped together and insulated for a minimum of 30’ from the merchandiser. Additional insulation is recommended wherever condensation drippage is objectionable.

7

Page 7
Image 7
hussman SCSS-SL manual Linesthrough Merchandisersthatare