hussman SCSS-SL manual Joint Trim, Waste Outlet And P-Trap

Models: SCSS SCSS-SL

1 24
Download 24 pages 45.19 Kb
Page 6
Image 6
JOINT TRIM

IGSSB-SCSS / SCSS-SL-0108

Installation (cont’d.)

CORNER WEDGES

Corner wedges are attached via front and rear camlocks. Use a 7mm Allen wrench to turn the locks. Do not over- tighten! Join the top by using a joint bracket (included in joint kit) with 3/8" bolts.

JOINT TRIM

After cases have been leveled and joined, and refrigera- tion, electrical, and wasted piping work completed, install the splashguards. Fasten along the top edge, or center, with #10 X 3/3" sheet metal screws.

DO NOT SEAL JOINT TRIM TO FLOOR!

Plumbing

WASTE OUTLET AND P-TRAP

The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture.

A 3/4" P-trap and threaded adapter are supplied with each fixture.The P-trap must be installed to prevent air leakage and insect entrance into the fixture.

NOTE: PVC-DWV solvent cement is recommended. Follow Hussmann’s instructions.

INSTALLING CONDENSATE DRAIN

Poorly or improperly installed condensate drains can se- riously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:

1.Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-trap supplied with the case.

2.When connecting condensate drains, the P-trap must be used as part of the condensate drain to prevent air leakage or insect entrance. Store plumb- ing system floor drains should be at least 14" off the center of the case to allow use of the P-trap pipe section. Never use two water seals in series in any one line. Double P-traps in series will cause a lock and prevent draining.

3.Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to main- tain the 1/8" pitch and to prevent warping.

4.Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.

5.Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.

6.Prevent condensate drains from freezing:

a.Do not install condensate drains in contact with non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.

b.Where condensate drains are located in dead air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing.The water seal should be insulated to prevent condensation.

Waste Outlet

 

 

Nipple

Inside Case

 

 

 

(All Models)

 

 

Coupling

 

 

90°

 

 

Remote

 

 

 

Air Gap

 

Refrigeration

 

 

Only!

 

 

 

6

Page 6
Image 6
hussman SCSS-SL manual Joint Trim, Waste Outlet And P-Trap