OUTPUT FUNCTIONS
The X4I will control the
+V
LOAD
SOLENOID
0V
NO | C | NC | NO | C | NC |
| OUT | C02 | IN |
| |
|
|
|
|
Two Wire Pressure Switch Connections
LOAD
SOLENOID
+V
0V
IR-PCB Internal Output Circuits
The C01 and C02 terminals of the
PRESSURE SWITCH REGULATION
For air compressors fitted with an
When connected, the pressure switch can be switched in and out of circuit automatically. If the X4I is stopped or experiences a failure or loss of power, pressure control will automatically revert back to the pressure switch and the compressor will continue to operate in “local” mode.
The local pressure settings of all compressors in the system should be set in a cascaded manner such that the system will operate normally in the event of X4I inoperability.
The NC (normally closed) and NO (normally open) terminal references of the
Lethal voltages may be present on the terminals of the air compressor pressure switch. Isolate the air compressor power supply before starting any work.
www.air.irco.com | 11 |
|
TIMER
NO | C | NC | NO | C | NC |
| OUT |
|
| IN |
|
C02
Three Wire Pressure Switch Connections
DIGITAL REGULATION CONTROL TERMINAL C01
A
This terminal provides volt free contact closure, referenced to a common terminal pin, for:
•Remote Load Enable (remote/local pressure regulation control)
•Remote Load (remote load/unload)
•Remote Variable Speed Regulation Inhibit (remote variable/fixed speed regulation control)
The “remote load enable” function provides the facility to change the compressor load regulation from internal control to a remote switching source (local/remote).
V The “remote variable/fixed” function provides for multiple variable speed compressor regulation control on variable speed compressor(s) equipped with this facility.
When using the “Variable/Fixed” function, the “V” terminal of the